Monitoring shows the state of the program running on the device on the MP STUDIO 2 screen in real time. You can check values on the ladder canvas, in the Data Table, on the Watch card and in the Value Trend graph, and change values on the device with value writes and forced I/O.
Ctrl+M (Run → Monitoring).Esc or Ctrl+M.If you edit the ladder while monitoring, monitoring is turned off with the notice Monitoring stopped because the program changed. To check the edited program, download it again and then turn monitoring back on.
If you edit the ladder after downloading and then turn monitoring on, the device pill shows Device program differs. The device is still running the previous program, so a value on the screen may belong to a different cell. When you see this tag, download again.
If the device stops responding during monitoring, the device pill and the status pills show No response. Check the cable, the device power and the communication port settings.
During monitoring, right-click a word cell and select Write Value to Memory, or select the cell and press Alt+Enter, to open the Write Value to Memory window.
A value outside the range of the data type is not sent, and the reason is shown. The program may overwrite the written value on the next scan.
During monitoring, right-click a bit cell and use Force ON or Force OFF to force that point on or off. The Force buttons in the Inspector do the same. You can check and release all forced points at once in the FORCE INPUT / OUTPUT window.
During monitoring, the cell menu contains Monitoring Off, the value display formats (Signed Decimal, Unsigned Decimal, Hexadecimal, Binary and Floating Point), Write Value to Memory, Force ON and Force OFF, and Add to Watch (address).
Select Run → Data Table to open the Data Table window. Register addresses to see their values in a table, write values or record a trend.
D10, M0 or R1 in the ① Address column and press Tab to move to the next cell. If the address has a symbol, it is shown in the Symbol column.BIT, WORD and so on). For word values, choose the display format, such as signed decimal, in the drop-down next to Value.0x (hexadecimal) or 0b (binary) values.You can add the address of a ladder cell to the Data Table directly.
If the Data Table is closed, it opens and the address is added. An address that is already registered is shown as Watching in the Inspector.
The addresses and values registered in the Data Table are also shown on the Watch card in the right column. If monitoring is on, the values on the Watch card keep updating even after you close the Data Table window.
Click Trend in the Data Table to open the Value Trend panel, which shows how the values of the registered addresses change over time.
Bit addresses (M0 in the figure) are shown as ON/OFF waveforms below the graph.
Recording stops automatically when the number of recorded rows reaches the limit. Nothing is drawn while monitoring is off.
Select Run → FORCE INPUT / OUTPUT to open the FORCE INPUT / OUTPUT window. Forced I/O makes an input point read a set value instead of its real signal, or makes an output point send a set value regardless of the ladder result.
Caution: Applied force values are stored in the device and stay in effect after a power cycle or a program re-download. To release them, press Clear, then Apply Force.
If both ON and OFF are set for one point, the device applies OFF. When points are forced, the device pill shows Forced N during monitoring; click it to open this window. Click Show Frames to see the communication frames that will be sent to the device.