Table of Contents

MPA F Module

The F module adds four PT100 temperature sensor inputs to an MPA Series controller. It supports two-wire and three-wire sensors. Up to five X and F modules can be combined, for a total of 20 channels.

Connect the sensor

For a two-wire sensor, connect the leads to the channel's A and B terminals and link B to B′. For a three-wire sensor, connect the leads to A, B, and B′. Check the terminal markings and sensor lead arrangement on the ordered product before wiring.

Read the temperature

In MP STUDIO, set the sensor channel and destination D memory in the PTEMP function block. For example, if CH0 writes 642 to D0, the temperature is 64.2°C. The stored value is in units of 0.1°C; the measurement range is −200 to +800°C.

Check before use

View two-wire and three-wire diagrams in the MPA manuals

Back to MPA Series