Table of Contents

MPA X Module

The X module adds four analog input channels to an MPA Series controller. Select the input type for each channel with its DIP switches. Up to five X and F modules can be combined, for a total of 20 channels.

Match the signal to the function block

Input signal MP STUDIO function block
DC 0–5 V, 0–10 V, or 0–20 mA ADC
DC 1–5 V or 4–20 mA ADC2
NTC temperature sensor (10 kΩ at 25°C, B value 3950) NTEMP

Set the DIP switches for the signal on each channel. In MP STUDIO, press [ to insert the function block, then set the channel, value range, and destination D memory. One channel cannot take an analog signal and an NTC sensor at the same time.

Example: read a voltage

Set CH0 to DC 0–5 V. In ADC, set the minimum to 0, maximum to 30000, and destination to D0. At 2.5 V, D0 reads approximately 15000. Sensor and conversion tolerances may affect the actual value.

For a 4–20 mA sensor, select ADC2. ADC does not treat 4 mA as the start of the measurement range.

Check before use

View DIP settings and wiring diagrams in the MPA manuals

Back to MPA Series