| MNET-32A32R is a communication slave I/O device that allows a master device such as a PC, HMI, or PLC to read digital inputs and control relay outputs over a communication link. | MNET-32A32R is a communication slave I/O device that allows a master device such as a PC, HMI, or PLC to read digital inputs and control relay outputs over a communication link. | ||
| - | Provides | + | The device provides |
| This product does not accept downloaded user programs. The master device controls I/O by reading or writing addresses on MNET-32A32R. | This product does not accept downloaded user programs. The master device controls I/O by reading or writing addresses on MNET-32A32R. | ||
| Line 95: | Line 95: | ||
| ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Value format ^ | ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Value format ^ | ||
| - | | X | Analog inputs | 4 points | X~X5, up to 20 points | 15bit, 0~32,767 \\ NTC mode: temperature ×10 | | + | | X | Analog inputs | 4 points | X~X5, up to 20 points | 15-bit, 0~32,767 \\ NTC mode: temperature ×10 | |
| | F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | −200~800℃ \\ Temperature ×10 | | | F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | −200~800℃ \\ Temperature ×10 | | ||
| - | | Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16bit, 0~65,535 | | + | | Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16-bit, 0~65,535 | |
| | K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | DC 5V, 30mA or less \\ Max. 1MHz | | | K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | DC 5V, 30mA or less \\ Max. 1MHz | | ||
| Line 106: | Line 106: | ||
| Configure analog inputs (X) and PT100Ω inputs (F) for **a combined maximum of 20 points**, and analog outputs (Y) and high-speed pulse outputs (K) for **a combined maximum of 12 points**. You cannot order a configuration that simply adds the maximum point count of every module. | Configure analog inputs (X) and PT100Ω inputs (F) for **a combined maximum of 20 points**, and analog outputs (Y) and high-speed pulse outputs (K) for **a combined maximum of 12 points**. You cannot order a configuration that simply adds the maximum point count of every module. | ||
| - | Options are assembled and shipped in the selected configuration; | + | Options are assembled and shipped in the selected configuration; |
| ==== Interpreting option values ==== | ==== Interpreting option values ==== | ||
| Line 155: | Line 155: | ||
| - Verify that the load is safe for an output test, then control the first output. The Modbus RTU internal address is '' | - Verify that the load is safe for an output test, then control the first output. The Modbus RTU internal address is '' | ||
| - After verification, | - After verification, | ||
| + | |||
| + | [[https:// | ||
| [[: | [[: | ||