en-us_products:mnet_8a8t
Differences
This shows you the differences between two versions of the page.
| Next revision | Previous revision | ||
| en-us_products:mnet_8a8t [2026/09/07 21:52] – 만듦 - 바깥 편집 127.0.0.1 | en-us_products:mnet_8a8t [2026/10/25 08:42] (current) – external edit 127.0.0.1 | ||
|---|---|---|---|
| Line 3: | Line 3: | ||
| MNET-8A8T is a communication slave I/O device that allows a master device such as a PC, HMI, or PLC to read digital inputs and control transistor outputs over a communication link. | MNET-8A8T is a communication slave I/O device that allows a master device such as a PC, HMI, or PLC to read digital inputs and control transistor outputs over a communication link. | ||
| - | Provides | + | The device provides |
| This product does not accept downloaded user programs. The master device controls I/O by reading or writing addresses on MNET-8A8T. | This product does not accept downloaded user programs. The master device controls I/O by reading or writing addresses on MNET-8A8T. | ||
| Line 31: | Line 31: | ||
| ===== Digital inputs ===== | ===== Digital inputs ===== | ||
| + | [[: | ||
| ^ Group ^ Input contacts ^ Communication address ^ Input configuration ^ | ^ Group ^ Input contacts ^ Communication address ^ Input configuration ^ | ||
| | Input 0~3 group | IN0~IN3 | Modbus 0~3 \\ Cnet P0000~P0003 | 4 isolated digital inputs \\ DC 5~24V \\ NPN/PNP inputs | | | Input 0~3 group | IN0~IN3 | Modbus 0~3 \\ Cnet P0000~P0003 | 4 isolated digital inputs \\ DC 5~24V \\ NPN/PNP inputs | | ||
| Line 39: | Line 40: | ||
| ===== Transistor outputs ===== | ===== Transistor outputs ===== | ||
| + | [[: | ||
| ^ Output contacts ^ Communication address ^ Output power ^ Output configuration ^ | ^ Output contacts ^ Communication address ^ Output power ^ Output configuration ^ | ||
| | OUT0~OUT7 | Modbus 32~39 \\ Cnet P0032~P0039 | Ext Vin+ \\ Ext Vin− | 8 isolated SINK transistor outputs \\ Max. DC 60V, 1A | | | OUT0~OUT7 | Modbus 32~39 \\ Cnet P0032~P0039 | Ext Vin+ \\ Ext Vin− | 8 isolated SINK transistor outputs \\ Max. DC 60V, 1A | | ||
| Line 85: | Line 87: | ||
| ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Value format ^ | ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Value format ^ | ||
| - | | X | Analog inputs | 4 points | X~X5, up to 20 points | 15bit, 0~32,767 \\ NTC mode: temperature ×10 | | + | | X | Analog inputs | 4 points | X~X5, up to 20 points | 15-bit, 0~32,767 \\ NTC mode: temperature ×10 | |
| | F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | Temperature ×10 | | | F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | Temperature ×10 | | ||
| - | | Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16bit, 0~65,535 | | + | | Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16-bit, 0~65,535 | |
| | K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | WIDTH fixed at 65,535 \\ Duty 0~65,535 | | | K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | WIDTH fixed at 65,535 \\ Duty 0~65,535 | | ||
| Line 94: | Line 96: | ||
| Configure analog inputs (X) and PT100Ω inputs (F) for **a combined maximum of 20 points**, and analog outputs (Y) and high-speed pulse outputs (K) for **a combined maximum of 12 points**. You cannot order a configuration that simply adds the maximum point count of every module. | Configure analog inputs (X) and PT100Ω inputs (F) for **a combined maximum of 20 points**, and analog outputs (Y) and high-speed pulse outputs (K) for **a combined maximum of 12 points**. You cannot order a configuration that simply adds the maximum point count of every module. | ||
| - | Options are assembled and shipped in the selected configuration; | + | Options are assembled and shipped in the selected configuration; |
| Products with optional modules are custom-built, | Products with optional modules are custom-built, | ||
| Line 145: | Line 147: | ||
| - Verify that the load is safe for an output test, then control the first output. The Modbus RTU internal address is '' | - Verify that the load is safe for an output test, then control the first output. The Modbus RTU internal address is '' | ||
| - After verification, | - After verification, | ||
| + | |||
| + | [[https:// | ||
| [[: | [[: | ||