en-us_products:mpino_16a16r
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revision | |||
| en-us_products:mpino_16a16r [2026/10/07 22:35] – external edit 127.0.0.1 | en-us_products:mpino_16a16r [2026/10/25 08:42] (current) – external edit 127.0.0.1 | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| ====== MPINO-16A16R ====== | ====== MPINO-16A16R ====== | ||
| - | MPINO-16A16R is a all-in-one industrial Arduino with 16 digital inputs and 16 relay outputs. Analog inputs, temperature sensor inputs, PWM outputs, high-speed inputs, and RS-485 communication are integrated on one PCB. | + | MPINO-16A16R is an all-in-one industrial Arduino with 16 digital inputs and 16 relay outputs. Analog inputs, temperature sensor inputs, PWM outputs, high-speed inputs, and RS-485 communication are integrated on one PCB. |
| Program the controller with Arduino IDE (Arduino C/C++) or MPINO STUDIO 2 (Arduino C/C++ & ladder logic). | Program the controller with Arduino IDE (Arduino C/C++) or MPINO STUDIO 2 (Arduino C/C++ & ladder logic). | ||
| Line 17: | Line 17: | ||
| | Power | - | Supply voltage | | Power | - | Supply voltage | ||
| | Digital inputs | | Digital inputs | ||
| - | | Relay outputs | + | | Relay outputs |
| - | | Analog inputs | + | | Analog inputs |
| | Temperature sensor inputs | | Temperature sensor inputs | ||
| | High-speed input | 4 points\\ (Non-isolated) | | High-speed input | 4 points\\ (Non-isolated) | ||
| - | | PWM outputs | + | | PWM outputs |
| | Communication Channels | | Communication Channels | ||
| | ::: | ::: | RS-485 | | ::: | ::: | RS-485 | ||
| Line 186: | Line 186: | ||
| [[: | [[: | ||
| ^ Group ^ Terminal ^ Arduino Pin ^ Contact ratings ^ Terminals and Wiring Example ^ | ^ Group ^ Terminal ^ Arduino Pin ^ Contact ratings ^ Terminals and Wiring Example ^ | ||
| - | | COM2 | R(32)~R(35) | D32~D35 | AC 250V or DC 30V, Max. 5A/1 points·15A/COM | {{: | + | | COM2 | R(32)~R(35) | D32~D35 | AC 250V or DC 30V, Max. 5A/1 point·15A/COM | {{: |
| - | | COM3 | R(36)~R(39) | D36~D39 | AC 250V or DC 30V, Max. 5A/1 points·15A/COM | ::: | | + | | COM3 | R(36)~R(39) | D36~D39 | AC 250V or DC 30V, Max. 5A/1 point·15A/COM | ::: | |
| - | | COM4 | R(40)~R(43) | D40~D43 | AC 250V or DC 30V, Max. 5A/1 points·15A/COM | ::: | | + | | COM4 | R(40)~R(43) | D40~D43 | AC 250V or DC 30V, Max. 5A/1 point·15A/COM | ::: | |
| - | | COM5 | R(44)~R(47) | D44~D47 | AC 250V or DC 30V, Max. 5A/1 points·15A/COM | ::: | | + | | COM5 | R(44)~R(47) | D44~D47 | AC 250V or DC 30V, Max. 5A/1 point·15A/COM | ::: | |
| Relay outputs are dry contacts that physically connect each group' | Relay outputs are dry contacts that physically connect each group' | ||
| Line 748: | Line 748: | ||
| **Related built-in functions** | **Related built-in functions** | ||
| - | === Function example · LS Industrial Systems Cnet SLave: ICnetMem(), ICnetAdr(), ICnetInit(), | + | === Function example · LS Industrial Systems Cnet Slave: ICnetMem(), ICnetAdr(), ICnetInit(), |
| **Function prototype** | **Function prototype** | ||
en-us_products/mpino_16a16r.1791380126.txt.gz · Last modified: by 127.0.0.1