 ===== Common Rules ===== ===== Common Rules =====
  
-The ''TON'' family uses a 10 ms tick; the ''TAON'' family uses a 100 ms tick. A number is a tick count, and time literals such as ''1h30m'', ''10s'', and ''500ms'' are accepted. Use ''T'' for a 16-bit timer and ''DT'' for a 32-bit timer. A bit contact for the timer address reads its done state. Initialize a retentive timer with a ladder RESET coil, not box-function ''RST''.+The ''TON'' family uses a 10 ms tick and the ''TAON'' family a 100 ms tick by default; you can change these units for each project in [[#timer_unit_settings|Timer Unit Settings]]. A number is a tick count, and time literals such as ''1h30m'', ''10s'', and ''500ms'' are accepted. If you enter a memory address such as ''D10'' as the preset, you can change the time while running, for example from an HMI ([[#set_the_preset_from_memory|Set the Preset from Memory]]). Use ''T'' for a 16-bit timer and ''DT'' for a 32-bit timer. A bit contact for the timer address reads its done state. Initialize a retentive timer with a ladder RESET coil, not box-function ''RST''.
  
 {{ :en-us_products:mpino_studio2:timer-current-done.svg?1000 |Timer current value and done state }} {{ :en-us_products:mpino_studio2:timer-current-done.svg?1000 |Timer current value and done state }}
Line 19: Line 19:
 | [[en-us_products:mpino_studio2:box_functions:timer:tmon|TMON]] | Starts one pulse when the input turns ON and holds the done state ON for the set time. | | [[en-us_products:mpino_studio2:box_functions:timer:tmon|TMON]] | Starts one pulse when the input turns ON and holds the done state ON for the set time. |
 | [[en-us_products:mpino_studio2:box_functions:timer:tmr|TMR]] | Accumulates time while the input is ON. | | [[en-us_products:mpino_studio2:box_functions:timer:tmr|TMR]] | Accumulates time while the input is ON. |
-| [[en-us_products:mpino_studio2:box_functions:timer:taon|TAON]] | Provides the same on-delay behavior as TON with a 100 ms tick. | +| [[en-us_products:mpino_studio2:box_functions:timer:taon|TAON]] | Provides the same on-delay behavior as TON with a default 100 ms tick. | 
-| [[en-us_products:mpino_studio2:box_functions:timer:taoff|TAOFF]] | Provides the same off-delay behavior as TOFF with a 100 ms tick. | +| [[en-us_products:mpino_studio2:box_functions:timer:taoff|TAOFF]] | Provides the same off-delay behavior as TOFF with a default 100 ms tick. | 
-| [[en-us_products:mpino_studio2:box_functions:timer:tapl|TAPL]] | Provides the same input-held pulse behavior as TPL with a 100 ms tick. | +| [[en-us_products:mpino_studio2:box_functions:timer:tapl|TAPL]] | Provides the same input-held pulse behavior as TPL with a default 100 ms tick. | 
-| [[en-us_products:mpino_studio2:box_functions:timer:tamon|TAMON]] | Provides the same one-shot pulse behavior as TMON with a 100 ms tick. | +| [[en-us_products:mpino_studio2:box_functions:timer:tamon|TAMON]] | Provides the same one-shot pulse behavior as TMON with a default 100 ms tick. | 
-| [[en-us_products:mpino_studio2:box_functions:timer:tamr|TAMR]] | Provides the same retentive behavior as TMR with a 100 ms tick. |+| [[en-us_products:mpino_studio2:box_functions:timer:tamr|TAMR]] | Provides the same retentive behavior as TMR with a default 100 ms tick. | 
 + 
 +===== Timer Unit Settings ===== 
 + 
 +The length of one timer tick is set for each project. Open **Settings → Memory Area Settings** (''Ctrl + Shift + M'') and choose the values under **Timer units** at the bottom of the window. The selected values are saved in the project (.mp2). 
 + 
 +^ Item ^ Box functions affected ^ Available values ^ Default ^ 
 +| ''T*'' timer unit | TON, TOFF, TPL, TMON, and TMR | 1 ms / 10 ms | 10 ms | 
 +| ''TA*'' timer unit | TAON, TAOFF, TAPL, TAMON, and TAMR | 10 ms / 100 ms / 1000 ms | 100 ms | 
 + 
 +The ''TA*'' unit must be larger than the ''T*'' unit. For example, if ''T*'' is 10 ms, you must choose 100 ms or more for ''TA*''. If the two values are the same, a warning appears and the settings cannot be saved. 
 + 
 +Changing the unit affects presets as follows. 
 + 
 +  * A preset entered as a number is a tick count. ''TON T0 100'' is 1 second with the default settings and 0.1 seconds after ''T*'' is changed to 1 ms. 
 +  * A preset entered with a time unit, such as ''1s'' or ''500ms'', keeps the same time with any setting. However, it causes a build error if it is not a multiple of the new unit (''15ms'' with a 10 ms unit) or exceeds the maximum tick count. 
 +  * The maximum time scales with the unit. ''T'' (16-bit) holds up to 65535 ticks, so with ''T*'' set to 1 ms it covers about 65 seconds. For longer times, use a ''TA*'' timer or a 32-bit ''DT''. 
 +  * In a project that does not use the default units, the actual time appears below a numeric preset. For example, in a project with ''T*'' set to 1 ms, ''TON T0 100'' shows ''100ms''. 
 + 
 +If you change the unit and save while timers are affected, the **Change timer units** window opens and shows how many box functions change and where they are in the ladder. 
 + 
 +^ Button ^ Action ^ 
 +| **Convert numbers, keep the time** | Converts numeric presets to the new unit so that the time stays the same. Example: changing from 10 ms to 1 ms turns ''TON T0 100'' into ''TON T0 1000'' | 
 +| **Keep numbers (time changes)** | Leaves the numbers as entered and changes only the unit. The time of numeric presets changes. | 
 +| **Cancel** | Does not change the unit. | 
 + 
 +> **Caution when changing the unit:** Comparison contacts such as ''T0 > 50'', ''MOV T0 D0'', ''T[0]'' in Arduino code, the current values in the Modbus 4000 range, the value in D10 of ''TON T0 D10'', and T values saved on the board by power-fail retention are tick counts, so they do not change automatically when the unit changes. Check these values yourself after changing the unit. Changing the unit also clears the ladder undo history. 
 + 
 +> **Note on the 1 ms unit:** 1 ms is the unit of measurement, not the accuracy. Completion is checked once per scan, so the actual completion can be late by about the scan time plus 1 ms. 
 + 
 +> **Caution for earlier versions:** A project whose timer units differ from the defaults (''T*'' 10 ms, ''TA*'' 100 ms) cannot be opened in an earlier version without this feature. 
 + 
 +===== Set the Preset from Memory ===== 
 + 
 +If you enter a memory address such as ''D10'' in the preset field instead of a number or time, the timer reads that memory's value as the preset on every scan. You can change the timer's time from an HMI (touch panel) or through communication by changing the memory value, without uploading the program again. The same rule applies to all 10 timers, whether the target is ''T'' or ''DT''. 
 + 
 +^ Type ^ Addresses you can use ^ Example ^ 
 +| WORD memory | ''D'', ''C'', ''T'', ''WP'', ''WM'' | ''TON T0 D10'', ''TON T0 WM1'' | 
 +| DWORD memory | ''DD'', ''DC'', ''DT'', ''DP'', ''DM'' | ''TON DT0 DD5'' | 
 +| Symbol | A symbol that points to one of the addresses above | ''TON T0 Speed'' (when ''Speed'' points to ''D10'') | 
 + 
 +Real numbers (''R''), bits (''M0'', ''D0.5'', ''WM0.3''), 8-bit views (''BM0''), Arduino variables, expressions (''D10+1''), and addresses outside the memory range cannot be used and cause a build error. ''T0'' in the preset field reads the current value, not the done state. 
 + 
 +^ Run condition ^ Memory value ^ Command entered ^ Expected result ^ 
 +| Left condition ON | D10=300 | ''TON T0 D10'' | 3 s later (default unit) → T0 done contact=ON | 
 +| Left condition ON | D10=500 | ''TON T0 D10'' | 5 s later (default unit) → T0 done contact=ON | 
 + 
 +> **Caution on memory values:** A memory value is a tick count, not a time. With the default units, ''TON T0 D10'' runs for 5 seconds when D10 is 500, and ''TAON T0 D10'' runs for 5 seconds when D10 is 50. If you change the [[#timer_unit_settings|timer units]], the same value gives a different time; the value in memory does not change automatically and is not converted by the Change timer units window. Check the values the HMI uses yourself after changing the unit. 
 + 
 +  * A change made while running takes effect immediately. Raising the value during timing continues counting up to the new value; lowering it below the current value ends the timer on the next scan. 
 +  * TON and TMR stay done even if the value is raised after completion. To time again from the start, turn the TON input OFF and then ON, and initialize TMR with a ladder RESET coil. 
 +  * If the value is 0, TON and TMR complete as soon as the input turns ON, and TOFF turns its done state OFF as soon as the input turns OFF. TPL and TMON end in the same scan, so their ON state is not visible. 
 +  * The value is read as unsigned. A value shown as -1 in monitoring is 65535 ticks. When a ''T'' target uses DWORD memory, a value larger than 65535 is also treated as 65535 ticks. 
 +  * A DWORD address in the preset field follows the rule in [[en-us_products:mpino_studio2:memory#memory_structure|Memory Structure]]: ''DD5'' is ''D10'' and ''D11''. This differs from the ''DT'' numbering rule for the target. 
 + 
 +> **Caution right after power-on:** The memory value is 0 until the HMI writes it, so during that time TON completes immediately and TPL and TMON produce no output. To keep the value through a power cycle, register that memory in [[en-us_products:mpino_studio2:menus_settings#eeprom_retain|EEPROM Retain]] (''Ctrl + Shift + E''). 
 + 
 +For the HMI side (addresses, scaling, and input limits), see [[:en-us_guide:hmi_connection:studio2:timer_preset|Changing a Timer Preset from the HMI]].
  
 ===== Related Documentation ===== ===== Related Documentation =====