MNET-8A8T

MNET-8A8T is a communication slave I/O device that allows a master device such as a PC, HMI, or PLC to read digital inputs and control transistor outputs over a communication link.

Provides 8 digital inputs and 8 SINK transistor outputs as standard. Select Modbus RTU Slave or LS Industrial Systems Cnet Slave when ordering.

This product does not accept downloaded user programs. The master device controls I/O by reading or writing addresses on MNET-8A8T.

Product Specifications

Category Quantity Terminals / Addresses Specifications
Product role - - Communication slave I/O
No user program
Power - +24V, GND, F.G DC 24V power terminals
Digital inputs 8 points
(Isolated)
IN0~IN7
Modbus 0~7
Cnet P0000~P0007
DC 5~24V
NPN/PNP inputs
Optocoupler isolation
4 points/1COM
Transistor outputs 8 points
(Isolated SINK)
OUT0~OUT7
Modbus 32~39
Cnet P0032~P0039
Max. DC 60V, 1A
Optocoupler isolation
Use external load power
Communication protocol Order option Modbus RTU Slave
LS Industrial Systems Cnet Slave
Select one of the two protocols when ordering
Communication Channels 1 channel each RS-232
RS-485
UART
Use the port wired to the master device
I²C 1 channel SDA, SCL CPU module terminals
Internal power - +5V, GND Int VCC terminals
Mounting - - 35mm DIN rail

Communication terminals

Identify the CPU module terminals for the communication interface used to connect the master device.

Communication interface Product terminal labels
RS-232 TX, RX, GND
RS-485 485+, 485−
UART TXD, RXD, GND

Digital inputs

See the one-channel digital-input check before wiring for the first time. →

Group Input contacts Communication address Input configuration
Input 0~3 group IN0~IN3 Modbus 0~3
Cnet P0000~P0003
4 isolated digital inputs
DC 5~24V
NPN/PNP inputs
Input 4~7 group IN4~IN7 Modbus 4~7
Cnet P0004~P0007
4 isolated digital inputs
DC 5~24V
NPN/PNP inputs

Each group of 4 inputs shares one COM terminal. The master device can read input states with Modbus RTU FC02 (Read Discrete Inputs).

Transistor outputs

See the one-channel SINK transistor-output check before wiring for the first time. →

Output contacts Communication address Output power Output configuration
OUT0~OUT7 Modbus 32~39
Cnet P0032~P0039
Ext Vin+
Ext Vin−
8 isolated SINK transistor outputs
Max. DC 60V, 1A

The output terminal block comprises OUT0~OUT7 and the external load power terminals Ext Vin+ and Ext Vin−. Its structure differs from the COM terminals of relay outputs.

In Modbus RTU, read output states with FC01 (Read Coils) and control outputs with FC05 or FC15.

Use an external load power supply. Use back-EMF protection such as a diode, TVS, or snubber for inductive loads including relays, solenoids, and motors.

Basic I/O communication addresses

Category Contact Modbus RTU internal address
(Decimal)
LS Industrial Systems Cnet HMI DEC Read / Write
Input IN0~IN7 0~7 P0000~P0007 10001~10008 Read
Output OUT0~OUT7 32~39 P0032~P0039 00033~00040 Read / Write
State - 1000 M0000 - -

The HMI DEC address is a 1-based display address entered on the HMI screen. Use the internal addresses in the table in Modbus RTU frames.

DIP switch settings

The baud-rate DIP switch has 3 bits; switches 1·2·3 have values 4·2·1 respectively. The leftmost switch is the most significant bit.

Set value Baud rate Switch 1 Switch 2 Switch 3
0 9,600bps OFF OFF OFF
1 14,400bps OFF OFF ON
2 19,200bps OFF ON OFF
3 28,800bps OFF ON ON
4 38,400bps ON OFF OFF
5 57,600bps ON OFF ON
6 76,800bps ON ON OFF
7 115,200bps ON ON ON

The slave-address DIP switch has 4 bits; switches 1·2·3·4 have values 8·4·2·1 respectively. Form the desired address by adding the values of the selected switches.

Setting example Switch 1
(8)
Switch 2
(4)
Switch 3
(2)
Switch 4
(1)
Address 0 OFF OFF OFF OFF
Address 1 OFF OFF OFF ON
Address 5 OFF ON OFF ON
Address 10 ON OFF ON OFF
Address 15 ON ON ON ON

Set the DIP switches with power off. The master device's baud rate, data bits, parity, and stop bits must match the communication settings of the delivered product.

Optional modules

Code Function Points per module Maximum configuration Value format
X Analog inputs 4 points X~X5, up to 20 points 15bit, 0~32,767
NTC mode: temperature ×10
F PT100Ω temperature sensor input 4 points F~F5, up to 20 points Temperature ×10
Y Analog outputs 3 points Y~Y4, up to 12 points 16bit, 0~65,535
K High-speed pulse outputs 6 points K~K2, up to 12 points WIDTH fixed at 65,535
Duty 0~65,535

The X module offers selectable DC 0~5V, DC 0~10V, 0~20mA, or NTC inputs. Connect a 2-wire or 3-wire PT100Ω sensor to the F module. The Y module offers selectable DC 0~5V, DC 0~10V, or 0~20mA outputs. The K module outputs DC 5V pulses at up to 1MHz.

Configure analog inputs (X) and PT100Ω inputs (F) for a combined maximum of 20 points, and analog outputs (Y) and high-speed pulse outputs (K) for a combined maximum of 12 points. You cannot order a configuration that simply adds the maximum point count of every module.

Options are assembled and shipped in the selected configuration; users cannot add or remove I/O or optional modules. Also see MNET Series option configuration guide.

Products with optional modules are custom-built, so exchanges or refunds may be difficult.

Interpreting option values

Option module communication addresses

Use the address ranges below that correspond to the installed optional modules. The slave-address DIP switch selects the station address of the product to communicate with; the addresses in this table select items to read or write within that product.

Module channel Modbus RTU internal address
(Decimal)
LS Industrial Systems Cnet
X1 0~3 2000~2003 D0000~D0003
X2 4~7 2004~2007 D0004~D0007
X3 - 2008~2011 D0008~D0011
X4 - 2012~2015 D0012~D0015
X5 - 2016~2019 D0016~D0019
Y1 0~2 2020~2022 D0020~D0022
Y2 3~5 2023~2025 D0023~D0025
Y3 6~8 2026~2028 D0026~D0028
Y4 9~11 2029~2031 D0029~D0031
F1 0~3 2040~2043 D0040~D0043
F2 4~7 2044~2047 D0044~D0047
F3 - 2048~2051 D0048~D0051
F4 - 2052~2055 D0052~D0055
F5 - 2056~2059 D0056~D0059
K1 PWM0~PWM5 2060~2065 D0060~D0065
K2 PWM6~PWM11 2066~2071 D0066~D0071

The confirmed separate addresses for the X module in NTC mode are as follows.

Module Modbus RTU internal address
(Decimal)
LS Industrial Systems Cnet
X1 NTC 2080~2083 D2080~D2083
X2 NTC 2084~2087 D2084~D2087

The Cnet addresses for NTC are D2080~D2087. Enter these addresses using their own notation, distinguishing it from other option addresses.

Communication startup sequence

  1. Verify that the ordered product's communication protocol matches the master device.
  2. Turn off power and wire the required RS-232, RS-485, or UART port.
  3. Set the baud-rate and slave-address DIP switches.
  4. Match the master device port, baud rate, data bits, parity, stop bits, and target slave address to the delivered product settings.
  5. Check wiring and settings, then turn on the power.
  6. Read the first input to check communication. The Modbus RTU internal address is 0 and the LS Industrial Systems Cnet address is P0000.
  7. Verify that the load is safe for an output test, then control the first output. The Modbus RTU internal address is 32 and the LS Industrial Systems Cnet address is P0032.
  8. After verification, apply all required addresses in order.