MNET Series

MNET Series is a family of communication slave products whose digital I/O, analog I/O, temperature sensor inputs, and high-speed pulse I/O can be controlled from a master device such as a PC, HMI, or PLC using Modbus or LS Industrial Systems Cnet.

The CPU module includes DIP switches for setting the baud rate and slave address.

Supports 1 RS-232 channel, 1 RS-485 channel, and 1 UART channel.

This product does not accept downloaded user programs. Select Modbus RTU Slave or LS Industrial Systems Cnet Slave when ordering.

How to read model names

  • The leading number in 8A, 16A, 32A, etc. is the number of digital inputs.
  • The number before R is the number of relay outputs.
  • The number before T is the number of transistor outputs.
  • 8A8R is a model with 8 digital inputs and 8 relay outputs.
  • 8A8T is a model with 8 digital inputs and 8 transistor outputs.

MNET Series comparison

Model Communication
Protocol
Digital inputs Relay outputs Transistor outputs RS-232 RS-485 UART
MNET-8A8R Modbus RTU
LS Industrial Systems Cnet
8 8 0 1 1 1
MNET-8A8T Modbus RTU
LS Industrial Systems Cnet
8 0 8 1 1 1
MNET-16A16R Modbus RTU
LS Industrial Systems Cnet
16 16 0 1 1 1
MNET-32A32R Modbus RTU
LS Industrial Systems Cnet
32 32 0 1 1 1

Optional modules provide analog I/O, temperature sensor inputs, and high-speed pulse I/O.

MNET Series specifications

Use the addresses for the communication protocol selected when ordering. The table shows each model's base digital input and output addresses.

Product Address type Modbus RTU addresses LS Cnet addresses
MNET-8A8R Digital inputs 0–7 P0000–P0007
Relay outputs 32–39 P0032–P0039
MNET-8A8T Digital inputs 0–7 P0000–P0007
Transistor outputs 32–39 P0032–P0039
MNET-16A16R Digital inputs 0–15 P0000–P0015
Relay outputs 32–47 P0032–P0047
MNET-32A32R Digital inputs 0–31 P0000–P0031
Relay outputs 32–63 P0032–P0063

Optional modules

The following optional modules can be added to the product configuration. The product is assembled and shipped in the selected configuration.
Users cannot add or remove I/O modules or optional modules.

Code Function Points per module Maximum configuration
X Analog inputs 4 points Up to 5 units, 20 points
F PT100Ω temperature sensor input 4 points Up to 5 units, 20 points
Y Analog outputs 3 points Up to 4 units, 12 points
K High-speed pulse outputs 6 points Up to 2 units, 12 points

The combined total of analog inputs and PT100Ω temperature sensor inputs cannot exceed 20 points.
The combined total of analog outputs and high-speed pulse outputs cannot exceed 12 points.
Products with optional modules are custom-built, so exchanges or refunds may be difficult.

Communication settings

Item Selection range Setting method
Communication protocol Modbus RTU Slave
LS Industrial Systems Cnet Slave
Select when ordering
Baud rate 9,600 / 14,400 / 19,200 / 28,800 / 38,400 / 57,600 / 76,800 / 115,200bps 3-bit DIP switch
Slave address 0~15 4-bit DIP switch
Communication terminals RS-232
RS-485
UART
Use the port wired to the master device