Table of Contents

MPA-64A64T

MPA Series is an assembled industrial PLC combining a CPU module with digital input and output modules.
Analog input/output, temperature sensor input, and high-speed pulse output modules can be added as options.
The selected I/O and optional modules are assembled and shipped as one product. Users cannot add or remove modules.

MPA-64A64T provides 64 digital inputs and 64 SINK transistor outputs.

Program with ladder logic using MP STUDIO.






MPA-64A64T connector guide

Product Specifications

Category Quantity Terminal / Item Specifications
Programming method - - MP STUDIO
MP STUDIO2
(Ladder logic program)
Power - Supply voltage DC 12~24V
For DC 24V, a power supply rated 0.5A or more is recommended
Digital inputs 64 points
(Isolated)
Module 0: P0~P7
Module 1: P8~P15
Module 2: P16~P23
Module 3: P24~P31
Module 4: P32~P39
Module 5: P40~P47
Module 6: P48~P55
Module 7: P56~P63
Operating input voltage DC 0~80V
HIGH detection: DC 5V or higher
Optocoupler isolation
Transistor outputs 64 points
(Isolated SINK)
Module 0: P64~P71
Module 1: P72~P79
Module 2: P80~P87
Module 3: P88~P95
Module 4: P96~P103
Module 5: P104~P111
Module 6: P112~P119
Module 7: P120~P127
P24: DC 5~24V
Load voltage DC 0~100V
Max. 1A/1 points, 8A/1COM
Optional modules up to 20 points Analog inputs
PT100Ω temperature sensor input
Optional specifications
up to 12 points Analog outputs
High-speed pulse outputs
Optional specifications
Communication Channels 1 channel each RS-232
RS-485
UART
I²C
Built into the CPU module
Memory - Flash
Data
256KB
8KB

Digital inputs

See the one-channel digital-input check before wiring for the first time. →

Module Group Input contacts Input configuration Terminal blocks and wiring examples
Module 0 COM0
COM1
P0~P3
P4~P7
8 isolated digital inputs
4 points/1COM
MPA-64A64T digital input wiring example
Module 1 COM0
COM1
P8~P11
P12~P15
8 isolated digital inputs
4 points/1COM
Module 2 COM0
COM1
P16~P19
P20~P23
8 isolated digital inputs
4 points/1COM
Module 3 COM0
COM1
P24~P27
P28~P31
8 isolated digital inputs
4 points/1COM
Module 4 COM0
COM1
P32~P35
P36~P39
8 isolated digital inputs
4 points/1COM
Module 5 COM0
COM1
P40~P43
P44~P47
8 isolated digital inputs
4 points/1COM
Module 6 COM0
COM1
P48~P51
P52~P55
8 isolated digital inputs
4 points/1COM
Module 7 COM0
COM1
P56~P59
P60~P63
8 isolated digital inputs
4 points/1COM

The diagram shows a wiring example for module 0. For other modules, use the corresponding contact numbers in the table. This example uses a DC 24V supply; each group can use PNP or NPN depending on its COM wiring.

The digital inputs are isolated by optocouplers. NPN or PNP switches and sensors can be used depending on the COM terminal wiring of each input module.

Transistor outputs

See the one-channel SINK transistor-output check before wiring for the first time. →

Module Output contacts Output power Output configuration Terminal blocks and wiring examples
Module 0 P64~P71 P24
N24
8 isolated SINK transistor outputs MPA-64A64T transistor output wiring example
Module 1 P72~P79 P24
N24
8 isolated SINK transistor outputs
Module 2 P80~P87 P24
N24
8 isolated SINK transistor outputs
Module 3 P88~P95 P24
N24
8 isolated SINK transistor outputs
Module 4 P96~P103 P24
N24
8 isolated SINK transistor outputs
Module 5 P104~P111 P24
N24
8 isolated SINK transistor outputs
Module 6 P112~P119 P24
N24
8 isolated SINK transistor outputs
Module 7 P120~P127 P24
N24
8 isolated SINK transistor outputs

The diagram shows a wiring example for module 0. For other modules, use the corresponding contact numbers in the table.

Connect DC 5~24V to P24 on each module and connect the supply GND to N24. When the output is ON, the output contact is connected to the GND supplied at N24.

Optional modules

Module Maximum points Function
Analog inputs 20 points DC 0~5V, DC 0~10V, 0~20mA or NTC temperature sensor input
PT100Ω temperature sensor input 20 points 2-wire or 3-wire PT100Ω temperature sensor input
Analog outputs 12 points DC 0~5V, DC 0~10V or 0~20mA output
High-speed pulse outputs 12 points Pulse output up to 1MHz

Communication and program upload

Function channel Terminals / Ports Usage Device wiring
Program upload and monitoring - DOWNLOAD Select as download port in MP STUDIO MPA-64A64T communication and program upload wiring example
RS-232 Channel 1 TX, RX, GND Use MP STUDIO communication port settings
RS-485 Channel 2 485+, 485- Use MP STUDIO communication port settings
UART channel 3 TXD, RXD, GND Use MP STUDIO communication port settings
I²C 1 channel SDA, SCL Master communication

The I²C diagram shows a connection example for a 5V device. Check the other device's signal voltage before connecting UART.

Status LED

Control the CPU module STATUS LED with the @SLED contact in MP STUDIO.

Development environment setup

  1. Connect the computer to the CPU module DOWNLOAD port with a USB cable.
  2. Check the download port's COM number in Device Manager.
  3. In MP STUDIO, open the MPA tab and select MPA-64A64R(T).
  4. Set the verified COM number as the download port, then download the ladder program.

Dimensions

Item Dimensions
Product width 244mm
Body height 108mm
Overall height Clip open: 120.42mm
Clip closed: 115.16mm
Product depth Body: 79mm
Maximum with terminals: 83mm
Mounting hole spacing 216mm
Mounting hole diameter Ø4mm
DIN rail 35mm
Front view Side view
Rear view

← Back to MPA Series comparison