| MNET-8A8R is a communication slave product whose digital I/O, analog I/O, temperature sensor inputs, and high-speed pulse I/O can be controlled from a master device such as a PC, HMI, or PLC using Modbus or LS Industrial Systems Cnet. | MNET-8A8R is a communication slave product whose digital I/O, analog I/O, temperature sensor inputs, and high-speed pulse I/O can be controlled from a master device such as a PC, HMI, or PLC using Modbus or LS Industrial Systems Cnet. | ||
| - | Consists | + | It consists |
| Select Modbus RTU Slave or LS Industrial Systems Cnet Slave in the options when ordering. | Select Modbus RTU Slave or LS Industrial Systems Cnet Slave in the options when ordering. | ||
| Line 15: | Line 15: | ||
| | Power | - | +24V, GND, F.G | DC 12~24V \\ For DC 24V, a power supply rated 0.5A or more is recommended | | Power | - | +24V, GND, F.G | DC 12~24V \\ For DC 24V, a power supply rated 0.5A or more is recommended | ||
| | Digital inputs | | Digital inputs | ||
| - | | Relay outputs | + | | Relay outputs |
| | Communication protocol | | Communication protocol | ||
| | Communication Channels | | Communication Channels | ||
| Line 89: | Line 89: | ||
| ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Value format ^ | ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Value format ^ | ||
| - | | X | Analog inputs | 4 points | X~X5, up to 20 points | 15bit, 0~32,767 \\ NTC mode: temperature ×10 | | + | | X | Analog inputs | 4 points | X~X5, up to 20 points | 15-bit, 0~32,767 \\ NTC mode: temperature ×10 | |
| | F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | −200~800℃ \\ Temperature ×10 | | | F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | −200~800℃ \\ Temperature ×10 | | ||
| - | | Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16bit, 0~65,535 | | + | | Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16-bit, 0~65,535 | |
| | K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | DC 5V, 30mA or less \\ Max. 1MHz | | | K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | DC 5V, 30mA or less \\ Max. 1MHz | | ||
| Line 100: | Line 100: | ||
| Configure analog inputs (X) and PT100Ω inputs (F) for **a combined maximum of 20 points**, and analog outputs (Y) and high-speed pulse outputs (K) for **a combined maximum of 12 points**. You cannot order a configuration that simply adds the maximum point count of every module. | Configure analog inputs (X) and PT100Ω inputs (F) for **a combined maximum of 20 points**, and analog outputs (Y) and high-speed pulse outputs (K) for **a combined maximum of 12 points**. You cannot order a configuration that simply adds the maximum point count of every module. | ||
| - | Options are assembled and shipped in the selected configuration; | + | Options are assembled and shipped in the selected configuration; |
| ==== Interpreting option values ==== | ==== Interpreting option values ==== | ||