en-us_products:mpa [2026/09/07 21:52] – 만듦 - 바깥 편집 127.0.0.1en-us_products:mpa [2026/09/15 15:28] (current) – external edit 127.0.0.1
Line 38: Line 38:
  
 Optional modules provide analog I/O, temperature sensor inputs, and high-speed pulse outputs. Optional modules provide analog I/O, temperature sensor inputs, and high-speed pulse outputs.
 +
 +===== MPA Series specifications =====
 +
 +Find each product's download cable, driver, and base I/O contact names. Option-module contact names depend on the ordered configuration and that module's specifications.
 +
 +^ Product ^ Download cable and driver ^ Contact type ^ Contact names / channels ^
 +| [[en-us_products:mpa_8a8r|MPA-8A8R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P7 |
 +| ::: | ::: | Relay outputs | P32–P39 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| ::: | ::: | Encoder inputs | SDA(A), SCL(B) |
 +| [[en-us_products:mpa_8a8t|MPA-8A8T]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P7 |
 +| ::: | ::: | Transistor outputs | P32–P39 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_16a16r|MPA-16A16R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P15 |
 +| ::: | ::: | Relay outputs | P32–P47 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_16a16t|MPA-16A16T]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P15 |
 +| ::: | ::: | Transistor outputs | P32–P47 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_16a32r|MPA-16A32R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P15 |
 +| ::: | ::: | Relay outputs | P32–P63 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_24a24r|MPA-24A24R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P23 |
 +| ::: | ::: | Relay outputs | P32–P55 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_24a24t|MPA-24A24T]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P23 |
 +| ::: | ::: | Transistor outputs | P32–P55 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_32a16r|MPA-32A16R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P31 |
 +| ::: | ::: | Relay outputs | P32–P47 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_32a32r|MPA-32A32R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P31 |
 +| ::: | ::: | Relay outputs | P32–P63 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_32a32t|MPA-32A32T]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P31 |
 +| ::: | ::: | Transistor outputs | P32–P63 |
 +| ::: | ::: | High-speed counter inputs | P0, P1 |
 +| ::: | ::: | Encoder inputs | P0(A), P2(B) \\ P1(A), P3(B) |
 +| [[en-us_products:mpa_48a48r|MPA-48A48R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P47 |
 +| ::: | ::: | Relay outputs | P64–P111 |
 +| [[en-us_products:mpa_48a48t|MPA-48A48T]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P47 |
 +| ::: | ::: | Transistor outputs | P64–P111 |
 +| [[en-us_products:mpa_64a64r|MPA-64A64R]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P63 |
 +| ::: | ::: | Relay outputs | P64–P127 |
 +| [[en-us_products:mpa_64a64t|MPA-64A64T]] | USB cable \\ [[https://www.ilogics.net/en-us/resources/downloads/driver/2|CP210x driver]] | Digital inputs | P0–P63 |
 +| ::: | ::: | Transistor outputs | P64–P127 |
  
 ===== Optional modules ===== ===== Optional modules =====
Line 45: Line 100:
  
 ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Key features ^ ^ Code ^ Function ^ Points per module ^ Maximum configuration ^ Key features ^
-| X | Analog inputs | 4 points | Up to 5 units, 20 points | Select DC 0~5V / 0~10V / 0(4)~20mA / NTC input | +| [[en-us_products:mpa_x|X]] | Analog inputs | 4 points | Up to 5 units, 20 points | Select DC 0~5V / 0~10V / 0(4)~20mA / NTC input | 
-| F | PT100Ω temperature sensor input | 4 points | Up to 5 units, 20 points | 2-wire or 3-wire PT100Ω input | +| [[en-us_products:mpa_f|F]] | PT100Ω temperature sensor input | 4 points | Up to 5 units, 20 points | 2-wire or 3-wire PT100Ω input | 
-| Y | Analog outputs | 3 points | Up to 4 units, 12 points | Select DC 0~5V / 0~10V / 0(4)~20mA output | +| [[en-us_products:mpa_y|Y]] | Analog outputs | 3 points | Up to 4 units, 12 points | Select DC 0~5V / 0~10V / 0(4)~20mA output | 
-| K | High-speed pulse outputs | 6 points | Up to 2 units, 12 points | DC 5V, Max. 1MHz |+| [[en-us_products:mpa_k|K]] | High-speed pulse outputs | 6 points | Up to 2 units, 12 points | DC 5V, Max. 1MHz |
  
 The combined total of analog inputs and PT100Ω temperature sensor inputs cannot exceed 20 points. \\ The combined total of analog inputs and PT100Ω temperature sensor inputs cannot exceed 20 points. \\