User Tools

Site Tools


en-us_products:mpa_32a16r

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
en-us_products:mpa_32a16r [2026/09/07 21:52] – 만듦 - 바깥 편집 127.0.0.1en-us_products:mpa_32a16r [2026/10/25 08:42] (current) – external edit 127.0.0.1
Line 1: Line 1:
 ====== MPA-32A16R ====== ====== MPA-32A16R ======
  
-MPA Series is an assembled industrial PLC combining a CPU module with digital input and output modules. \\+The MPA Series comprises modular industrial PLCs assembled from a CPU module and digital input and output modules. \\
 Analog input/output, temperature sensor input, and high-speed pulse output modules can be added as options. \\ Analog input/output, temperature sensor input, and high-speed pulse output modules can be added as options. \\
 The selected I/O and optional modules are assembled and shipped as one product. Users cannot add or remove modules. The selected I/O and optional modules are assembled and shipped as one product. Users cannot add or remove modules.
Line 23: Line 23:
 |  Power  |  -  |  Supply voltage  | DC 12~24V \\ For DC 24V, a power supply rated 0.5A or more is recommended  | |  Power  |  -  |  Supply voltage  | DC 12~24V \\ For DC 24V, a power supply rated 0.5A or more is recommended  |
 |  Digital inputs  |  32 points \\ (Isolated)  |  Module 0: P0~P15 \\ Module 1: P16~P31  | Operating input voltage DC 0~80V \\ HIGH detection: DC 5V or higher \\ Optocoupler isolation  | |  Digital inputs  |  32 points \\ (Isolated)  |  Module 0: P0~P15 \\ Module 1: P16~P31  | Operating input voltage DC 0~80V \\ HIGH detection: DC 5V or higher \\ Optocoupler isolation  |
-|  Relay outputs  |  16 points \\ (Isolated dry contacts)  |  Module 0: P32~P47  | DC 0~30V or AC 0~250V \\ Max. 5A/1 points, 8A/1COM  |+|  Relay outputs  |  16 points \\ (Isolated dry contacts)  |  Module 0: P32~P47  | DC 0~30V or AC 0~250V \\ Max. 5A/1 point, 8A/1COM  |
 |  High-speed counter inputs  |  2 points \\ (Isolated)  |  P0, P1  | Max. 8kHz \\ Shared with digital inputs  | |  High-speed counter inputs  |  2 points \\ (Isolated)  |  P0, P1  | Max. 8kHz \\ Shared with digital inputs  |
 |  Encoder Inputs  |  2 points \\ (Isolated)  |  P0(A)·P2(B) \\ P1(A)·P3(B)  | Max. 8kHz \\ Shared with high-speed counter inputs  | |  Encoder Inputs  |  2 points \\ (Isolated)  |  P0(A)·P2(B) \\ P1(A)·P3(B)  | Max. 8kHz \\ Shared with high-speed counter inputs  |
Line 33: Line 33:
 ===== Digital inputs ===== ===== Digital inputs =====
  
 +[[:en-us_guide:wiring#digital_input_one_channel_check|See the one-channel digital-input check before wiring for the first time. →]]
 ^ Module ^ Group ^ Input contacts ^ Input configuration ^ Terminal blocks and wiring examples ^ ^ Module ^ Group ^ Input contacts ^ Input configuration ^ Terminal blocks and wiring examples ^
 | Module 0 | COM0 \\ COM1 | P0~P7 \\ P8~P15 | 16 isolated digital inputs \\ 8 points/1COM \\ P0/P1 share high-speed counter inputs |  {{:en-us_products:mpa-input-16-wiring.svg?628|MPA-32A16R digital input wiring example}}  | | Module 0 | COM0 \\ COM1 | P0~P7 \\ P8~P15 | 16 isolated digital inputs \\ 8 points/1COM \\ P0/P1 share high-speed counter inputs |  {{:en-us_products:mpa-input-16-wiring.svg?628|MPA-32A16R digital input wiring example}}  |
Line 43: Line 44:
 ===== Relay outputs ===== ===== Relay outputs =====
  
 +[[:en-us_guide:wiring#relay_output_one_channel_check|See the one-channel relay-output check before wiring for the first time. →]]
 ^ Module ^ Group ^ Output contacts ^ Contact configuration ^ Terminal blocks and wiring examples ^ ^ Module ^ Group ^ Output contacts ^ Contact configuration ^ Terminal blocks and wiring examples ^
 | Module 0 | COM0~COM3 | P32~P47 | 16 relay outputs \\ 4 points/1COM |  {{:en-us_products:mpa-relay-16-wiring.svg?740|MPA-32A16R relay output wiring example}}  | | Module 0 | COM0~COM3 | P32~P47 | 16 relay outputs \\ 4 points/1COM |  {{:en-us_products:mpa-relay-16-wiring.svg?740|MPA-32A16R relay output wiring example}}  |
Line 104: Line 106:
 ^ Rear view ^  ^ ^ Rear view ^  ^
 |  [[https://www.ilogics.net/docs/_media/products:mpa-32a16r-dimension-rear.svg|{{ :en-us_products:mpa-32a16r-dimension-rear.svg?nolink&360 }}]]  |  | |  [[https://www.ilogics.net/docs/_media/products:mpa-32a16r-dimension-rear.svg|{{ :en-us_products:mpa-32a16r-dimension-rear.svg?nolink&360 }}]]  |  |
 +
 +[[https://www.ilogics.net/en-us/products/mpa-32a16r|View MPA-32A16R price and purchase options]]
  
 [[:en-us_products:mpa|← Back to MPA Series comparison]] [[:en-us_products:mpa|← Back to MPA Series comparison]]
  
en-us_products/mpa_32a16r.1788785570.txt.gz · Last modified: by 127.0.0.1

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki