MNET-32A32R is a communication slave I/O device that allows a master device such as a PC, HMI, or PLC to read digital inputs and control relay outputs over a communication link.
Provides 32 digital inputs and 32 relay outputs as standard. Select Modbus RTU Slave or LS Industrial Systems Cnet Slave when ordering.
This product does not accept downloaded user programs. The master device controls I/O by reading or writing addresses on MNET-32A32R.
| Category | Quantity | Terminals / Addresses | Specifications |
|---|---|---|---|
| Product role | - | - | Communication slave I/O No user program |
| Module configuration | 5 modules | CPU 2 digital inputs modules 2 relay outputs modules | Assembled and shipped in the selected configuration |
| Power | - | +24V, GND, F.G | DC 24V power terminals |
| Digital inputs | 32 points (Isolated) | 0~31 Modbus 0~31 Cnet P0000~P0031 | DC 5~24V NPN/PNP inputs Optocoupler isolation 8 points/1COM |
| Relay outputs | 32 points (Isolated) | 0~31 Modbus 32~63 Cnet P0032~P0063 | Dry contacts Max. DC 30V or AC 300V, 5A 4 points/1COM |
| Communication protocol | Order option | Modbus RTU Slave LS Industrial Systems Cnet Slave | Select one of the two protocols when ordering |
| Communication Channels | 1 channel each | RS-232 RS-485 UART | Use the port wired to the master device |
| I²C | 1 channel | SDA, SCL | CPU module terminals |
| Internal power | - | +5V, GND | Int VCC terminals |
| Mounting | - | - | 35mm DIN rail |
Identify the CPU module terminals for the communication interface used to connect the master device.
| Communication interface | Product terminal labels |
|---|---|
| RS-232 | TX, RX, GND |
| RS-485 | 485+, 485− |
| UART | TXD, RXD, GND |
See the one-channel digital-input check before wiring for the first time. →
| Group | Number of inputs | Communication address | Input configuration |
|---|---|---|---|
| Input 0~7 group | 0~7 | Modbus 0~7 Cnet P0000~P0007 | 8 isolated digital inputs DC 5~24V NPN/PNP inputs |
| Input 8~15 group | 8~15 | Modbus 8~15 Cnet P0008~P0015 | 8 isolated digital inputs DC 5~24V NPN/PNP inputs |
| Input 16~23 group | 16~23 | Modbus 16~23 Cnet P0016~P0023 | 8 isolated digital inputs DC 5~24V NPN/PNP inputs |
| Input 24~31 group | 24~31 | Modbus 24~31 Cnet P0024~P0031 | 8 isolated digital inputs DC 5~24V NPN/PNP inputs |
Digital inputs share one COM terminal for every 8 points, giving a total of 4 COM groups.
See the one-channel relay-output check before wiring for the first time. →
| Group | Number of outputs | Communication address | Output configuration |
|---|---|---|---|
| Output 0~3 group | 0~3 | Modbus 32~35 Cnet P0032~P0035 | 4 dry relay contacts |
| Output 4~7 group | 4~7 | Modbus 36~39 Cnet P0036~P0039 | 4 dry relay contacts |
| Output 8~11 group | 8~11 | Modbus 40~43 Cnet P0040~P0043 | 4 dry relay contacts |
| Output 12~15 group | 12~15 | Modbus 44~47 Cnet P0044~P0047 | 4 dry relay contacts |
| Output 16~19 group | 16~19 | Modbus 48~51 Cnet P0048~P0051 | 4 dry relay contacts |
| Output 20~23 group | 20~23 | Modbus 52~55 Cnet P0052~P0055 | 4 dry relay contacts |
| Output 24~27 group | 24~27 | Modbus 56~59 Cnet P0056~P0059 | 4 dry relay contacts |
| Output 28~31 group | 28~31 | Modbus 60~63 Cnet P0060~P0063 | 4 dry relay contacts |
Relay outputs share one COM terminal for every 4 points, giving a total of 8 COM groups. The output contact rating is up to DC 30V or AC 300V, 5A.
Inputs use 8 points/1COM and outputs use 4 points/1COM, so the COM groupings differ between the two terminal blocks.
| Category | Points | Modbus RTU internal address (Decimal) | LS Industrial Systems Cnet | Operation |
|---|---|---|---|---|
| Input | 0~31 | 0~31 | P0000~P0031 | Read |
| Output | 0~31 | 32~63 | P0032~P0063 | Read / Write |
| State | - | 1000 | M0000 | Check status |
For this model, input addresses end at 31 and output addresses start at 32, making the two ranges contiguous.
The baud-rate DIP switch has 3 bits; switches 1·2·3 have values 4·2·1 respectively. The leftmost switch is the most significant bit.
| Set value | Baud rate | Switch 1 | Switch 2 | Switch 3 |
|---|---|---|---|---|
| 0 | 9,600bps | OFF | OFF | OFF |
| 1 | 14,400bps | OFF | OFF | ON |
| 2 | 19,200bps | OFF | ON | OFF |
| 3 | 28,800bps | OFF | ON | ON |
| 4 | 38,400bps | ON | OFF | OFF |
| 5 | 57,600bps | ON | OFF | ON |
| 6 | 76,800bps | ON | ON | OFF |
| 7 | 115,200bps | ON | ON | ON |
The slave-address DIP switch has 4 bits; switches 1·2·3·4 have values 8·4·2·1 respectively.
| Setting example | Switch 1 (8) | Switch 2 (4) | Switch 3 (2) | Switch 4 (1) |
|---|---|---|---|---|
| Address 0 | OFF | OFF | OFF | OFF |
| Address 1 | OFF | OFF | OFF | ON |
| Address 5 | OFF | ON | OFF | ON |
| Address 10 | ON | OFF | ON | OFF |
| Address 15 | ON | ON | ON | ON |
Set the DIP switches with power off. The master device's baud rate, data bits, parity, and stop bits must match the communication settings of the delivered product.
| Code | Function | Points per module | Maximum configuration | Value format |
|---|---|---|---|---|
| X | Analog inputs | 4 points | X~X5, up to 20 points | 15bit, 0~32,767 NTC mode: temperature ×10 |
| F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | −200~800℃ Temperature ×10 |
| Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16bit, 0~65,535 |
| K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | DC 5V, 30mA or less Max. 1MHz |
The X module offers selectable DC 0~5V, DC 0~10V, 0(4)~20mA, or NTC inputs. Connect a 2-wire or 3-wire PT100Ω sensor to the F module. The Y module offers selectable DC 0~5V, DC 0~10V, or 0(4)~20mA outputs.
Available option combinations depend on the product. Products with optional modules are assembled in the selected configuration, so exchanges or refunds after purchase may be difficult.
Configure analog inputs (X) and PT100Ω inputs (F) for a combined maximum of 20 points, and analog outputs (Y) and high-speed pulse outputs (K) for a combined maximum of 12 points. You cannot order a configuration that simply adds the maximum point count of every module.
Options are assembled and shipped in the selected configuration; users cannot add or remove I/O or optional modules. Also see MNET Series option configuration guide.
Use the address ranges below that correspond to the installed optional modules. The slave-address DIP switch selects the station address of the product to communicate with; the addresses in this table select items to read or write within that product.
| Module | channel | Modbus RTU internal address (Decimal) | LS Industrial Systems Cnet |
|---|---|---|---|
| X1 | 0~3 | 2000~2003 | D0000~D0003 |
| X2 | 4~7 | 2004~2007 | D0004~D0007 |
| X3 | - | 2008~2011 | D0008~D0011 |
| X4 | - | 2012~2015 | D0012~D0015 |
| X5 | - | 2016~2019 | D0016~D0019 |
| Y1 | 0~2 | 2020~2022 | D0020~D0022 |
| Y2 | 3~5 | 2023~2025 | D0023~D0025 |
| Y3 | 6~8 | 2026~2028 | D0026~D0028 |
| Y4 | 9~11 | 2029~2031 | D0029~D0031 |
| F1 | 0~3 | 2040~2043 | D0040~D0043 |
| F2 | 4~7 | 2044~2047 | D0044~D0047 |
| F3 | - | 2048~2051 | D0048~D0051 |
| F4 | - | 2052~2055 | D0052~D0055 |
| F5 | - | 2056~2059 | D0056~D0059 |
| K1 | PWM0~PWM5 | 2060~2065 | D0060~D0065 |
| K2 | PWM6~PWM11 | 2066~2071 | D0066~D0071 |
The confirmed separate addresses for the X module in NTC mode are as follows.
| Module | Modbus RTU internal address (Decimal) | LS Industrial Systems Cnet |
|---|---|---|
| X1 NTC | 2080~2083 | D2080~D2083 |
| X2 NTC | 2084~2087 | D2084~D2087 |
The Cnet addresses for NTC are D2080~D2087. Enter these addresses using their own notation, distinguishing it from other option addresses.
0 and the LS Industrial Systems Cnet address is P0000.32 and the LS Industrial Systems Cnet address is P0032.