MNET-8A8R is a communication slave product whose digital I/O, analog I/O, temperature sensor inputs, and high-speed pulse I/O can be controlled from a master device such as a PC, HMI, or PLC using Modbus or LS Industrial Systems Cnet.
Consists of a CPU module (1 RS-232 channel, 1 RS-485 channel, and 1 UART channel) and an I/O module (8 digital inputs and 8 relay outputs).
Select Modbus RTU Slave or LS Industrial Systems Cnet Slave in the options when ordering.
| Category | Quantity | Terminals / Addresses | Specifications |
|---|---|---|---|
| Product role | - | - | Communication slave I/O No user program |
| Power | - | +24V, GND, F.G | DC 12~24V For DC 24V, a power supply rated 0.5A or more is recommended |
| Digital inputs | 8 points (Isolated) | 0~7 Modbus 0~7 Cnet P0000~P0007 | Operating input voltage DC 0~80V HIGH detection: DC 5V or higher Optocoupler isolation |
| Relay outputs | 8 points (Isolated dry contacts) | 0~7 Modbus 32~39 Cnet P0032~P0039 | DC 0~30V or AC 0~250V Max. 5A/1 points, 8A/1COM |
| Communication protocol | Order option | Modbus RTU Slave LS Industrial Systems Cnet Slave | Select one of the two protocols when ordering |
| Communication Channels | 1 channel each | RS-232 RS-485 UART | Use the port wired to the master device |
| I²C | 1 channel | SDA, SCL | CPU module terminals |
| Internal power | - | +5V, GND | Int VCC terminals |
| Mounting | - | - | 35mm DIN rail |
Check the CPU module communication terminals and internal power terminals.
| Communication interface | Product terminal labels | Device connection example |
|---|---|---|
| RS-232 | TX, RX, GND | |
| RS-485 | 485+, 485− | |
| UART | TXD, RXD, GND | |
| I²C / internal power | SDA, SCL / +5V, GND |
Cross the transmit and receive terminals for RS-232 and UART; match polarities for RS-485. For UART, verify that the signal voltage is compatible with the other device.
See the one-channel digital-input check before wiring for the first time. →
Each group of 4 inputs shares one COM terminal, and both groups support PNP or NPN wiring. For PNP, connect COM to supply −; for NPN, connect COM to supply +.
The DC 24V shown in the diagram is a wiring example. The operating input voltage is DC 0~80V, and HIGH detection requires DC 5V or higher.
See the one-channel relay-output check before wiring for the first time. →
Relay outputs share one COM terminal for every 4 points. The output contact rating is DC 0~30V or AC 0~250V, with a maximum allowable current of 5A/1 point and 8A/1COM.
| Category | Points | Modbus RTU internal address (Decimal) | LS Industrial Systems Cnet | Operation |
|---|---|---|---|---|
| Input | 0~7 | 0~7 | P0000~P0007 | Read |
| Output | 0~7 | 32~39 | P0032~P0039 | Read / Write |
| State | - | 1000 | M0000 | Check status |
The baud-rate DIP switch has 3 bits; switches 1·2·3 have values 4·2·1 respectively. The leftmost switch is the most significant bit.
| Set value | Baud rate | Switch 1 | Switch 2 | Switch 3 | Switch appearance |
|---|---|---|---|---|---|
| 0 | 9,600bps | OFF | OFF | OFF | |
| 1 | 14,400bps | OFF | OFF | ON | |
| 2 | 19,200bps | OFF | ON | OFF | |
| 3 | 28,800bps | OFF | ON | ON | |
| 4 | 38,400bps | ON | OFF | OFF | |
| 5 | 57,600bps | ON | OFF | ON | |
| 6 | 76,800bps | ON | ON | OFF | |
| 7 | 115,200bps | ON | ON | ON | |
The slave-address DIP switch has 4 bits; switches 1·2·3·4 have values 8·4·2·1 respectively. Form the desired address by adding the values of the selected switches.
| Setting example | Switch 1 (8) | Switch 2 (4) | Switch 3 (2) | Switch 4 (1) | Switch appearance |
|---|---|---|---|---|---|
| Address 0 | OFF | OFF | OFF | OFF | |
| Address 1 | OFF | OFF | OFF | ON | |
| Address 5 | OFF | ON | OFF | ON | |
| Address 10 | ON | OFF | ON | OFF | |
| Address 15 | ON | ON | ON | ON | |
Set the DIP switches with power off. The master device's baud rate, data bits, parity, and stop bits must match the communication settings of the delivered product.
| Code | Function | Points per module | Maximum configuration | Value format |
|---|---|---|---|---|
| X | Analog inputs | 4 points | X~X5, up to 20 points | 15bit, 0~32,767 NTC mode: temperature ×10 |
| F | PT100Ω temperature sensor input | 4 points | F~F5, up to 20 points | −200~800℃ Temperature ×10 |
| Y | Analog outputs | 3 points | Y~Y4, up to 12 points | 16bit, 0~65,535 |
| K | High-speed pulse outputs | 6 points | K~K2, up to 12 points | DC 5V, 30mA or less Max. 1MHz |
The X module offers selectable DC 0~5V, DC 0~10V, 0(4)~20mA, or NTC inputs. Connect a 2-wire or 3-wire PT100Ω sensor to the F module. The Y module offers selectable DC 0~5V, DC 0~10V, or 0(4)~20mA outputs.
Available option combinations depend on the product. Products with optional modules are assembled in the selected configuration, so exchanges or refunds after purchase may be difficult.
Configure analog inputs (X) and PT100Ω inputs (F) for a combined maximum of 20 points, and analog outputs (Y) and high-speed pulse outputs (K) for a combined maximum of 12 points. You cannot order a configuration that simply adds the maximum point count of every module.
Options are assembled and shipped in the selected configuration; users cannot add or remove I/O or optional modules. Also see MNET Series option configuration guide.
Use the address ranges below that correspond to the installed optional modules. The slave-address DIP switch selects the station address of the product to communicate with; the addresses in this table select items to read or write within that product.
| Module | channel | Modbus RTU internal address (Decimal) | LS Industrial Systems Cnet |
|---|---|---|---|
| X1 | 0~3 | 2000~2003 | D0000~D0003 |
| X2 | 4~7 | 2004~2007 | D0004~D0007 |
| X3 | - | 2008~2011 | D0008~D0011 |
| X4 | - | 2012~2015 | D0012~D0015 |
| X5 | - | 2016~2019 | D0016~D0019 |
| Y1 | 0~2 | 2020~2022 | D0020~D0022 |
| Y2 | 3~5 | 2023~2025 | D0023~D0025 |
| Y3 | 6~8 | 2026~2028 | D0026~D0028 |
| Y4 | 9~11 | 2029~2031 | D0029~D0031 |
| F1 | 0~3 | 2040~2043 | D0040~D0043 |
| F2 | 4~7 | 2044~2047 | D0044~D0047 |
| F3 | - | 2048~2051 | D0048~D0051 |
| F4 | - | 2052~2055 | D0052~D0055 |
| F5 | - | 2056~2059 | D0056~D0059 |
| K1 | PWM0~PWM5 | 2060~2065 | D0060~D0065 |
| K2 | PWM6~PWM11 | 2066~2071 | D0066~D0071 |
The confirmed separate addresses for the X module in NTC mode are as follows.
| Module | Modbus RTU internal address (Decimal) | LS Industrial Systems Cnet |
|---|---|---|
| X1 NTC | 2080~2083 | D2080~D2083 |
| X2 NTC | 2084~2087 | D2084~D2087 |
The Cnet addresses for NTC are D2080~D2087. Enter these addresses using their own notation, distinguishing it from other option addresses.
0 and the LS Industrial Systems Cnet address is P0000.32 and the LS Industrial Systems Cnet address is P0032.