MNET Series

MNET-8A8R

MNET-8A8R Communication I/O Controller

I/O at a glance
8 DI / 8 Relay / RS-232 / RS-485 / UART / I²C

MNET-8A8R is a communication-type industrial I/O controller with 8 isolated digital inputs and 8 relay outputs. Onboard RS-232, RS-485, UART, I²C, operating as a Modbus RTU or LS ELECTRIC Cnet slave — the protocol is chosen at order time. It runs no user program: a master device such as a PC, HMI or PLC reads and writes the I/O over the serial link. DIN-rail mountable for automation, testing, HMI integration and machine control.

$121.00 In stock
Options
Communication protocolRequired

Chosen once, at order time. It cannot be changed to the other protocol after the unit ships.

Analogue input module (X)

Adding an expansion module means the unit is dismantled and re-assembled to order, so such an order is difficult to exchange or refund. Some combinations are not available on some models; if yours cannot be built we will contact you.

PT100Ω temperature input module (F)
Analogue output module (Y)
Pulse output module (K)
Total$121.00
Shipping

International shipping (EMS · DHL · UPS) — calculated at checkout by destination & weight

Dispatch

Ships the next business day (regardless of order time)

Large orders may take 1 extra day to dispatch

Returns & Exchange

Cancel before dispatch · request a return/exchange after delivery

Overview

/ OVERVIEW

MNET-8A8R is a communication-type industrial I/O controller with 8 isolated digital inputs and 8 relay outputs. Onboard RS-232, RS-485, UART, I²C, operating as a Modbus RTU or LS ELECTRIC Cnet slave — the protocol is chosen at order time. It runs no user program: a master device such as a PC, HMI or PLC reads and writes the I/O over the serial link. DIN-rail mountable for automation, testing, HMI integration and machine control.

Key features

  • Controlled entirely over the bus — no firmware to write. A PC, HMI or PLC master reads and writes the I/O as Modbus RTU or LS ELECTRIC Cnet slave (protocol chosen at order time).
  • 8 opto-isolated digital inputs, NPN/PNP selectable
  • 8 relay outputs for AC/DC dry-contact switching
  • Industrial communication: RS-485, RS-232, UART, I²C · Modbus RTU
  • DIN-rail 35 mm mountable, isolated field I/O for the factory floor

Specifications

/ SPEC
Digital inputs8
Relay outputs8
RS-2321ch
RS-4851ch
UART1ch
I²C1ch
Modbus RTUYes
LS CnetYes

Communication and terminalsMODBUS RTU / LS CNET SLAVE

The program runs on your master, not on this unit

MNET-8A8R is a communication slave. A PC, SCADA station, HMI or PLC opens a serial link, and from that moment the field I/O is simply a set of addresses it reads and writes. There is no firmware to write, no toolchain to install, and no board to flash — which is why the protocol is fixed once, at order time.

  • Three serial terminals

    RS-232, RS-485 and TTL UART are all brought out to screw poles. Wire the one your master uses.

  • Slave, by design

    The station number is called a slave address, and it is set on the unit itself. The master owns the conversation.

  • Chosen at order time

    Modbus RTU slave or LS ELECTRIC Cnet slave. One unit speaks one of them, and it cannot be changed after shipping.

Terminal strip (silkscreen)

RS-232TXRXGNDRS-485485+485−UARTTXDRXDGNDI2C / Int VCCSDASCL+5VGND+5V · GND = Int VCCPOWER+24VGNDF.G

Poles are drawn exactly as the product silkscreens them. The +5V pole belongs to Int VCC; its allowed current is not stated in any source, so no figure is printed here.

GroupPolesCount
RS-232TX · RX · GND3-pole
RS-485485+ · 485−2-pole
UARTTXD · RXD · GND3-pole
I2C / Int VCCSDA · SCL · +5V · GND4-pole
POWER+24V · GND · F.G3-pole

Before you wire it

  • Match the protocol you ordered to the driver on the master. A Modbus master cannot talk to a Cnet unit.
  • RS-485 is a two-wire pair: check 485+ / 485− polarity, and consider twisted pair, shielding and termination on a long run.
  • F.G is a field ground pole, not a signal return. GND is the return.

System layout

MASTERPC · SCADAHMIPLCRS-232RS-485UARTMNETremote I/OSLAVESensors · switchesValves · lamps

The three links are alternatives, not three simultaneous channels — wire the port your master actually uses.

Digital input and relay output8 IN / 8 OUT · ISOLATED

Eight isolated inputs and eight dry relay contacts

Both sides are split into two groups of four, and each group has a common of its own. That is what 8P, 4P 1COM means: you can run one group off a 24 V sensor loop and the other off a 5 V one, or switch two circuits that share nothing.

Digital input

ItemRating
Points8P, 4P 1COM
Input voltageDC 5V ~ 24V
Input typeNPN / PNP
IsolationPhotocoupler isolated

4P 1COM — points 0–3 share one common and points 4–7 share another, on each side.

Relay output

ItemRating
Points8P, 4P 1COM
Contact ratingMax. DC30V or AC300V 5A
Output typeRelay (Dry Contact)
IsolationRelay isolated

Ratings

  • The contact rating is the manufacturer's figure: Max. DC30V or AC300V 5A. Do not exceed it.
  • Relay contacts are dry: the load supply is yours to provide. Fit a diode, TVS or snubber across an inductive load.
  • NPN or PNP is decided by how you wire the common, so check the sensor's polarity before power-up.

I/O register mapDECIMAL ADDRESSES

Every point has a number, and that number is the whole interface

Once the link is up, using this unit is reading and writing decimal addresses. Inputs are 0 to 7, outputs are 32 to 39, and the status bit is 1000. The LS ELECTRIC Cnet side maps onto the same points in the P area.

Terminals and their addresses

Modbus RTULS CnetDIGITAL INPUT00P000011P000122P000233P0003COMDIGITAL INPUT44P000455P000566P000677P0007COMModbus RTULS CnetRELAY OUTPUT032P0032133P0033234P0034335P0035COMRELAY OUTPUT436P0036537P0037638P0038739P0039COM

Addresses are decimal, exactly as the manufacturer's map prints them. COM poles carry no address because the master never addresses a common.

Status bit

ItemModbus RTULS Cnet
STATUS1000M0000

Reading the map

  • These are the unit's internal addresses. An HMI that expects 1-based display addresses will need its own offset — check what your driver sends on the wire.
  • Modbus function codes are not published for this model, so none are printed here. Confirm them with ILOGICS before writing the master.

Baud rate and slave addressDIP SWITCH

Two dip blocks, one rule: the left switch is worth the most

Communication speed and station number are set on the unit, with no software involved. Both blocks read the same way — the leftmost switch is the most significant bit, and a slider pushed toward the ON mark counts.

How to read the switches

BAUDRATEON142231shown: 6 → 76,800 bpsADDRESSON18243241shown: 10

Both patterns were re-derived from the manufacturer's artwork by measuring every slider: all 24 published patterns match this rule.

SettingBaud rate
09,600
114,400
219,200
328,800
438,400
557,600
676,800
7115,200

Slave address 0 – 15

AddressSwitches ON
0
14
23
33 · 4
42
52 · 4
62 · 3
72 · 3 · 4
81
91 · 4
101 · 3
111 · 3 · 4
121 · 2
131 · 2 · 4
141 · 2 · 3
151 · 2 · 3 · 4

Setting it

  • Master and unit must agree on speed, data bits, parity and stop bits. Only speed and address are set here; the rest is not published for this model.
  • The factory default position is not documented, so read the switches on the unit rather than assuming one.
  • Every unit on one RS-485 bus needs a different address.

Expansion I/O modulesX · F · Y · K

Analog, temperature and pulse, added at order time

The base unit is digital in and relay out. Analog input, PT100 temperature, analog output and pulse output arrive as modules built into the same enclosure — an 8A8R-X2FYK is an 8A8R with two X modules, one F, one Y and one K. Choose them in the options above; the address each one answers on is listed below.

ModuleTypeDetailMaximum
XAnalog input4 points (DC 0–5 V, DC 0–10 V, 0(4)–20 mA, NTC sensor)up to 5 modules (20 points)
FPT100Ω temperature input4 points (−200 °C to +800 °C, 2-wire or 3-wire)up to 5 modules (20 points)
YAnalog output3 points (DC 0–5 V, DC 0–10 V, 0(4)–20 mA, 16-bit)up to 4 modules (12 points)
KPulse output6 points (DC 5 V, 30 mA max, up to 1 MHz)up to 2 modules (12 points)

Addresses by module

ModuleChannelsModbus RTULS Cnet
X10 ~ 32000 ~ 2003D0000 ~ D0003
X24 ~ 72004 ~ 2007D0004 ~ D0007
X32008 ~ 2011D0008 ~ D0011
X42012 ~ 2015D0012 ~ D0015
X52016 ~ 2019D0016 ~ D0019
F10 ~ 32040 ~ 2043D0040 ~ D0043
F24 ~ 72044 ~ 2047D0044 ~ D0047
F32048 ~ 2051D0048 ~ D0051
F42052 ~ 2055D0052 ~ D0055
F52056 ~ 2059D0056 ~ D0059
Y10 ~ 22020 ~ 2022D0020 ~ D0022
Y23 ~ 52023 ~ 2025D0023 ~ D0025
K10 ~ 12060 ~ 2065D0060 ~ D0065
K22 ~ 32066 ~ 2071D0066 ~ D0071

Channels are shown where the manufacturer's map labels them. X3–X5 and F3–F5 are drawn with their addresses only, so only the addresses are given.

Reading the value

ModuleValue on the wire
XAnalog sent as 15-bit (0–32,767) · in NTC mode, temperature × 10 (21.3 °C → 213)
FTemperature × 10 is sent (21.3 °C → 213)
YReceives 16-bit (0–65,535) and drives the voltage / current output
KWIDTH fixed at 65,535 · duty received as 0–65,535

X module — NTC mode addresses

ModuleModbus RTULS Cnet
X12080 ~ 2083D2080 ~ D2083
X22084 ~ 2087D2084 ~ D2087

An X module set to NTC mode is read from these registers, not from its analog addresses above. The manufacturer's map prints this block for X1 and X2 only.

Before ordering a module

  • Adding a module means dismantling and reassembling the unit, so exchange and refund are difficult after purchase.
  • Some combinations are not possible; ILOGICS will contact you if an order cannot be built as specified.
  • Only Y1 and Y2 are listed: the manufacturer's map draws a third and fourth analog-output module with more addresses than the module's own 12-point maximum allows. Ask ILOGICS before ordering three or more Y modules.
  • Changing the pulse frequency or the number of pulse outputs is a made-to-order change — ask ILOGICS.

Downloads

/ FILES

FAQ

How many I/O points does the MNET-8A8R have?

The MNET-8A8R provides 8 isolated digital inputs and 8 relay outputs, with onboard RS-485, RS-232, UART, I²C communication. See the specification table for the full breakdown.

Does the MNET-8A8R support Modbus RTU?

Yes, as a SLAVE. The MNET-8A8R answers a master — a PC program, HMI or PLC — over RS-232, RS-485 or UART. The protocol is chosen when you order: Modbus RTU slave or LS ELECTRIC Cnet slave. It is never the master, and it runs no user program.