MNET-8A8R

MNET-8A8R Communication I/O Controller

I/O at a glance
8 DI / 8 Relay / RS-232 / RS-485 / UART / I²C

MNET-8A8R is a communication-type industrial I/O controller with 8 isolated digital inputs and 8 relay outputs. Onboard RS-232, RS-485, UART, I²C, operating as a Modbus RTU or LS ELECTRIC Cnet slave — the protocol is chosen at order time. It runs no user program: a master device such as a PC, HMI or PLC reads and writes the I/O over the serial link. DIN-rail mountable for automation, testing, HMI integration and machine control.

$115.50 In stock
Options
Communication protocolRequired

Chosen once, at order time. It cannot be changed to the other protocol after the unit ships.

Analogue input module (X)
PT100Ω temperature input module (F)
Analogue output module (Y)
Pulse output module (K)
Total$115.50

Shipping

International shipping (EMS) — calculated at checkout by destination & weight

Shipping weight 350 g (per unit)

Dispatch

Ships the next business day (regardless of order time)

Large orders may take 1 extra day to dispatch

Returns & Exchange

Cancel before dispatch · request a return/exchange after delivery

Key features

/ FEATURES
  • Controlled entirely over the bus — no firmware to write. A PC, HMI or PLC master reads and writes the I/O as Modbus RTU or LS ELECTRIC Cnet slave (protocol chosen at order time).
  • 8 opto-isolated digital inputs, NPN/PNP selectable
  • 8 relay outputs for AC/DC dry-contact switching
  • Industrial communication: RS-485, RS-232, UART, I²C · Modbus RTU
  • DIN-rail 35 mm mountable, isolated field I/O for the factory floor

Specifications

/ SPEC
Digital inputs8
Relay outputs8
RS-2321ch
RS-4851ch
UART1ch
I²C1ch
Modbus RTUYes
LS CnetYes

Communication terminals

MNET-8A8R is a communication slave: a PC, SCADA station, HMI or PLC opens one serial link and the field I/O becomes a set of addresses it reads and writes. The protocol — Modbus RTU or LS ELECTRIC Cnet — is fixed at order time and cannot be changed after shipping.

TerminalSilkscreen polesCount
RS-232TX · RX · GND3-pole
RS-485485+ · 485−2-pole
UARTTXD · RXD · GND3-pole
I2C / Int VCCSDA · SCL · +5V · GND4-pole
POWER+24V · GND · F.G3-pole
MASTERPC · SCADAHMIPLCRS-232RS-485UARTMNETremote I/OSLAVESensors · switchesValves · lamps

The three links are alternatives, not three simultaneous channels — wire the port your master actually uses.

Communication start-up sequence

  1. Confirm the protocol you ordered — Modbus RTU slave or LS ELECTRIC Cnet slave. One unit speaks one of them.
  2. With the power off, wire ONE of the serial ports — RS-232 · RS-485 · UART — to your master.
  3. Set the baud rate and the slave address (0 – 15) on the unit's dip switches.
  4. Match the master to those settings: baud rate, data bits, parity, stop bits and the slave address it targets.
  5. Apply power on the POWER terminal (+24V · GND · F.G).
  6. Read one input point to prove the link — Modbus 0 / Cnet P0000.
  7. Then drive one output point — Modbus 32 / Cnet P0032.
  8. Once both answer, map the full address list into your master's tag table.

Digital input and relay output

8 isolated inputs and 8 dry relay contacts. Each side divides into groups with a common of its own — the inputs into 2 of 4, the relay outputs into 2 of 4 — and the two sides are wired independently.

Digital input

ItemRating
Points8P, 4P 1COM
Input voltageDC 5V ~ 24V
Input typeNPN / PNP
IsolationPhotocoupler isolated

Relay output

ItemRating
Points8P, 4P 1COM
Contact ratingMax. DC30V or AC300V 5A
Output typeRelay (Dry Contact)
IsolationRelay isolated

Inputs: 4 points per common, so 2 commons. Relay outputs: 4 points per common, so 2 commons. The two sides are wired independently.

Basic I/O addresses

Once the link is up, using this unit is reading and writing decimal addresses: inputs 0 to 7, outputs 32 to 39, status bit 1000. The LS ELECTRIC Cnet side maps the same points onto its P area.

Modbus RTULS CnetDIGITAL INPUT00P000011P000122P000233P0003COMDIGITAL INPUT44P000455P000566P000677P0007COMModbus RTULS CnetRELAY OUTPUT032P0032133P0033234P0034335P0035COMRELAY OUTPUT436P0036537P0037638P0038739P0039COM

Addresses are decimal, exactly as the manufacturer's map prints them. COM poles carry no address because the master never addresses a common.

ItemPointsModbus RTULS CnetAccess
Digital input8 pt0 ~ 7P0000 ~ P0007Read
Relay output8 pt32 ~ 39P0032 ~ P0039Read / Write
Status bit1 pt1000M0000Read

Modbus function codes are not published for this model, so none are printed here. Confirm them with ILOGICS before writing the master.

DIP switch settings

Communication speed and station number are set on the unit itself, with no software involved: in both blocks the leftmost switch is the most significant bit and a slider pushed toward ON counts. Every unit on one RS-485 bus needs a station number of its own, and the range is 0 – 15.

BAUDRATEON ▲142231shown: 6 → 76,800 bpsADDRESSON ▲18243241shown: 10
SettingBaud rate
09,600
114,400
219,200
328,800
438,400
557,600
676,800
7115,200
Slave addressSwitches ON
0—
14
23
33 · 4
42
52 · 4
62 · 3
72 · 3 · 4
81
91 · 4
101 · 3
111 · 3 · 4
121 · 2
131 · 2 · 4
141 · 2 · 3
151 · 2 · 3 · 4

Option modules

Analog input, PT100Ω temperature, analog output and pulse output arrive as modules built into the same enclosure, chosen in the options above. The name 8A8R-X2FYK means 8A8R plus two X modules, one F, one Y and one K.

ModuleTypeDetailMaximum
XAnalog input4 points (DC 0–5 V, DC 0–10 V, 0(4)–20 mA, NTC sensor)up to 5 modules (20 points)
FPT100Ω temperature input4 points (−200 °C to +800 °C, 2-wire or 3-wire)up to 5 modules (20 points)
YAnalog output3 points (DC 0–5 V, DC 0–10 V, 0(4)–20 mA, 16-bit)up to 4 modules (12 points)
KPulse output6 points (DC 5 V, 30 mA max, up to 1 MHz)up to 2 modules (12 points)

Reading the value

ModuleValue on the wire
XAnalog sent as 15-bit (0–32,767) · in NTC mode, temperature × 10 (21.3 °C → 213)
FTemperature × 10 is sent (21.3 °C → 213)
YReceives 16-bit (0–65,535) and drives the voltage / current output
KWIDTH fixed at 65,535 · duty received as 0–65,535

Option module addresses

ModuleChannelsModbus RTULS Cnet
X10 ~ 32000 ~ 2003D0000 ~ D0003
X24 ~ 72004 ~ 2007D0004 ~ D0007
X3—2008 ~ 2011D0008 ~ D0011
X4—2012 ~ 2015D0012 ~ D0015
X5—2016 ~ 2019D0016 ~ D0019
F10 ~ 32040 ~ 2043D0040 ~ D0043
F24 ~ 72044 ~ 2047D0044 ~ D0047
F3—2048 ~ 2051D0048 ~ D0051
F4—2052 ~ 2055D0052 ~ D0055
F5—2056 ~ 2059D0056 ~ D0059
Y10 ~ 22020 ~ 2022D0020 ~ D0022
Y23 ~ 52023 ~ 2025D0023 ~ D0025
Y36 ~ 82026 ~ 2028D0026 ~ D0028
Y49 ~ 112029 ~ 2031D0029 ~ D0031
K10 ~ 12060 ~ 2065D0060 ~ D0065
K22 ~ 32066 ~ 2071D0066 ~ D0071

Channels are shown where the manufacturer's map labels them. X3–X5 and F3–F5 are drawn with their addresses only, so only the addresses are given.

NTC modeModbus RTULS Cnet
X12080 ~ 2083D2080 ~ D2083
X22084 ~ 2087D2084 ~ D2087

An X module set to NTC mode is read from these registers, not from its analog addresses above. The manufacturer's map prints this block for X1 and X2 only.

Changing the pulse frequency or the number of pulse outputs is a made-to-order change — ask ILOGICS.

Important notesX · F · Y · K

Expansion modules (X · F · Y · K) are built into the same enclosure as the base unit, in the configuration you order. That is why the combinations have limits.

Before you order

  • Adding an expansion module means the unit is assembled to your order, so such an order is difficult to exchange or refund.
  • Analogue input (X) and PT100Ω temperature input (F) — up to 20 points between them.
  • Analogue output (Y) and Pulse output (K) — up to 12 points between them.
  • A combination that cannot be built is disabled in the option selector, so it cannot be chosen.

FAQ

How many I/O points does the MNET-8A8R have?▾

The MNET-8A8R provides 8 isolated digital inputs and 8 relay outputs, with onboard RS-485, RS-232, UART, I²C communication. See the specification table for the full breakdown.

Does the MNET-8A8R support Modbus RTU?▾

Yes, as a SLAVE. The MNET-8A8R answers a master — a PC program, HMI or PLC — over RS-232, RS-485 or UART. The protocol is chosen when you order: Modbus RTU slave or LS ELECTRIC Cnet slave. It is never the master, and it runs no user program.