MNET-8A8R communication I/O controller — front view

MNET Series

MNET-8A8R

MNET-8A8R Communication I/O Controller

I/O at a glance
8 DI / 8 Relay / RS-232 / RS-485 / UART / I²C

MNET-8A8R is a communication-type industrial I/O controller with 8 isolated digital inputs and 8 relay outputs. Onboard RS-232, RS-485, UART, I²C, operating as a Modbus RTU or LS ELECTRIC Cnet slave — the protocol is chosen at order time. It runs no user program: a master device such as a PC, HMI or PLC reads and writes the I/O over the serial link. DIN-rail mountable for automation, testing, HMI integration and machine control.

$115.50 In stock
Options
Communication protocolRequired

Chosen once, at order time. It cannot be changed to the other protocol after the unit ships.

Analog input module (X)
PT100Ω temperature input module (F)
Analog output module (Y)
Pulse output module (K)
Total$115.50

Shipping

EMS or international air parcel — choose at checkout; rates depend on destination and weight

Shipping weight 350 g (per unit)

Dispatch

Ships the next business day (regardless of order time)

Large orders may take 1 extra day to dispatch

Returns & Exchange

Cancel before dispatch · request a return/exchange after delivery

Products ordered with the “Expansion module” option are modified to your order before shipping, so they cannot be returned or exchanged for a change of mind.

Key features

/ FEATURES
  • Controlled entirely over the bus — no firmware to write. A PC, HMI or PLC master reads and writes the I/O as Modbus RTU or LS ELECTRIC Cnet slave (protocol chosen at order time).
  • 8 opto-isolated digital inputs, NPN/PNP selectable
  • 8 relay outputs for AC/DC dry-contact switching
  • Industrial communication: RS-485, RS-232, UART, I²C · Modbus RTU
  • DIN-rail 35 mm mountable, isolated field I/O for the factory floor

Specifications

/ SPEC
Digital inputs8
Relay outputs8
RS-2321ch
RS-4851ch
UART1ch
I²C1ch
Modbus RTUYes
LS CnetYes

Communication terminals

MNET-8A8R is a communication slave: a PC, SCADA station, HMI or PLC opens one serial link and the field I/O becomes a set of addresses it reads and writes. The protocol — Modbus RTU or LS ELECTRIC Cnet — is fixed at order time and cannot be changed after shipping.

TerminalSilkscreen polesCount
RS-232Silkscreen polesTX · RX · GNDCount3-pole
RS-485Silkscreen poles485+ · 485−Count2-pole
UARTSilkscreen polesTXD · RXD · GNDCount3-pole
I2C / Int VCCSilkscreen polesSDA · SCL · +5V · GNDCount4-pole
POWERSilkscreen poles+24V · GND · F.GCount3-pole
MASTERPC · SCADAHMIPLCRS-232RS-485UARTMNETremote I/OSLAVESensors · switchesValves · lamps

The three links are alternatives, not three simultaneous channels — wire the port your master actually uses.

Communication start-up sequence

  1. Confirm the protocol you ordered — Modbus RTU slave or LS ELECTRIC Cnet slave. One unit speaks one of them.
  2. With the power off, wire ONE of the serial ports — RS-232 · RS-485 · UART — to your master.
  3. Set the baud rate and the slave address (0 – 15) on the unit's dip switches.
  4. Match the master to those settings: baud rate, data bits, parity, stop bits and the slave address it targets.
  5. Apply power on the POWER terminal (+24V · GND · F.G).
  6. Read one input point to prove the link — Modbus 0 / Cnet P0000.
  7. Then drive one output point — Modbus 32 / Cnet P0032.
  8. Once both answer, map the full address list into your master's tag table.

Digital input and relay output

8 isolated inputs and 8 dry relay contacts. Each side divides into groups with a common of its own — the inputs into 2 of 4, the relay outputs into 2 of 4 — and the two sides are wired independently.

Digital input

ItemRating
PointsRating8P, 4P 1COM
Input voltageRatingDC 5V ~ 24V
Input typeRatingNPN / PNP
IsolationRatingPhotocoupler isolated

Relay output

ItemRating
PointsRating8P, 4P 1COM
Contact ratingRatingMax. DC30V or AC300V 5A
Output typeRatingRelay (Dry Contact)
IsolationRatingRelay isolated

Inputs: 4 points per common, so 2 commons. Relay outputs: 4 points per common, so 2 commons. The two sides are wired independently.

Basic I/O addresses

Once the link is up, using this unit is reading and writing decimal addresses: inputs 0 to 7, outputs 32 to 39, status bit 1000. The LS ELECTRIC Cnet side maps the same points onto its P area.

Modbus RTULS CnetDIGITAL INPUT00P000011P000122P000233P0003COMDIGITAL INPUT44P000455P000566P000677P0007COMModbus RTULS CnetRELAY OUTPUT032P0032133P0033234P0034335P0035COMRELAY OUTPUT436P0036537P0037638P0038739P0039COM

Addresses are decimal, exactly as the manufacturer's map prints them. COM poles carry no address because the master never addresses a common.

ItemPointsModbus RTULS CnetAccess
Digital inputPoints8 ptModbus RTU0 ~ 7LS CnetP0000 ~ P0007AccessRead
Relay outputPoints8 ptModbus RTU32 ~ 39LS CnetP0032 ~ P0039AccessRead / Write
Status bitPoints1 ptModbus RTU1000LS CnetM0000AccessRead

Modbus function codes are not published for this model, so none are printed here. Confirm them with ILOGICS before writing the master.

DIP switch settings

Communication speed and station number are set on the unit itself, with no software involved: in both blocks the leftmost switch is the most significant bit and a slider pushed toward ON counts. Every unit on one RS-485 bus needs a station number of its own, and the range is 0 – 15.

BAUDRATEON ▲142231shown: 6 → 76,800 bpsADDRESSON ▲18243241shown: 10
SettingBaud rate
0Baud rate9,600
1Baud rate14,400
2Baud rate19,200
3Baud rate28,800
4Baud rate38,400
5Baud rate57,600
6Baud rate76,800
7Baud rate115,200
Slave addressSwitches ON
0Switches ON—
1Switches ON4
2Switches ON3
3Switches ON3 · 4
4Switches ON2
5Switches ON2 · 4
6Switches ON2 · 3
7Switches ON2 · 3 · 4
8Switches ON1
9Switches ON1 · 4
10Switches ON1 · 3
11Switches ON1 · 3 · 4
12Switches ON1 · 2
13Switches ON1 · 2 · 4
14Switches ON1 · 2 · 3
15Switches ON1 · 2 · 3 · 4

Option modules

Analog input, PT100Ω temperature, analog output and pulse output arrive as modules built into the same enclosure, chosen in the options above. The name 8A8R-X2FYK means 8A8R plus two X modules, one F, one Y and one K.

ModuleTypeDetailMaximum
XTypeAnalog inputDetail4 points (DC 0–5 V, DC 0–10 V, 0(4)–20 mA, NTC sensor)Maximumup to 5 modules (20 points)
FTypePT100Ω temperature inputDetail4 points (−200 °C to +800 °C, 2-wire or 3-wire)Maximumup to 5 modules (20 points)
YTypeAnalog outputDetail3 points (DC 0–5 V, DC 0–10 V, 0(4)–20 mA, 16-bit)Maximumup to 4 modules (12 points)
KTypePulse outputDetail6 points (DC 5 V, 30 mA max, up to 1 MHz)Maximumup to 2 modules (12 points)

Reading the value

ModuleValue on the wire
XValue on the wireAnalog sent as 15-bit (0–32,767) · in NTC mode, temperature × 10 (21.3 °C → 213)
FValue on the wireTemperature × 10 is sent (21.3 °C → 213)
YValue on the wireReceives 16-bit (0–65,535) and drives the voltage / current output
KValue on the wireWIDTH fixed at 65,535 · duty received as 0–65,535

Option module addresses

ModuleChannelsModbus RTULS Cnet
X1Channels0 ~ 3Modbus RTU2000 ~ 2003LS CnetD0000 ~ D0003
X2Channels4 ~ 7Modbus RTU2004 ~ 2007LS CnetD0004 ~ D0007
X3Channels—Modbus RTU2008 ~ 2011LS CnetD0008 ~ D0011
X4Channels—Modbus RTU2012 ~ 2015LS CnetD0012 ~ D0015
X5Channels—Modbus RTU2016 ~ 2019LS CnetD0016 ~ D0019
F1Channels0 ~ 3Modbus RTU2040 ~ 2043LS CnetD0040 ~ D0043
F2Channels4 ~ 7Modbus RTU2044 ~ 2047LS CnetD0044 ~ D0047
F3Channels—Modbus RTU2048 ~ 2051LS CnetD0048 ~ D0051
F4Channels—Modbus RTU2052 ~ 2055LS CnetD0052 ~ D0055
F5Channels—Modbus RTU2056 ~ 2059LS CnetD0056 ~ D0059
Y1Channels0 ~ 2Modbus RTU2020 ~ 2022LS CnetD0020 ~ D0022
Y2Channels3 ~ 5Modbus RTU2023 ~ 2025LS CnetD0023 ~ D0025
Y3Channels6 ~ 8Modbus RTU2026 ~ 2028LS CnetD0026 ~ D0028
Y4Channels9 ~ 11Modbus RTU2029 ~ 2031LS CnetD0029 ~ D0031
K1Channels0 ~ 1Modbus RTU2060 ~ 2065LS CnetD0060 ~ D0065
K2Channels2 ~ 3Modbus RTU2066 ~ 2071LS CnetD0066 ~ D0071

Channels are shown where the manufacturer's map labels them. X3–X5 and F3–F5 are drawn with their addresses only, so only the addresses are given.

NTC modeModbus RTULS Cnet
X1Modbus RTU2080 ~ 2083LS CnetD2080 ~ D2083
X2Modbus RTU2084 ~ 2087LS CnetD2084 ~ D2087

An X module set to NTC mode is read from these registers, not from its analog addresses above. The manufacturer's map prints this block for X1 and X2 only.

Changing the pulse frequency or the number of pulse outputs is a made-to-order change — ask ILOGICS.

Important notes X · F · Y · K

Expansion modules (X · F · Y · K) are built into the same enclosure as the base unit, in the configuration you order. That is why the combinations have limits.

Before you order

  • Adding an expansion module means the unit is assembled to your order, so such an order is difficult to exchange or refund.
  • Analog input (X) and PT100Ω temperature input (F) — up to 20 points between them.
  • Analog output (Y) and Pulse output (K) — up to 12 points between them.
  • A combination that cannot be built is disabled in the option selector, so it cannot be chosen.

FAQ

How many I/O points does the MNET-8A8R have?▾

The MNET-8A8R provides 8 isolated digital inputs and 8 relay outputs, with onboard RS-485, RS-232, UART, I²C communication. See the specification table for the full breakdown.

Does the MNET-8A8R support Modbus RTU?▾

Yes, as a SLAVE. The MNET-8A8R answers a master — a PC program, HMI or PLC — over RS-232, RS-485 or UART. The protocol is chosen when you order: Modbus RTU slave or LS ELECTRIC Cnet slave. It is never the master, and it runs no user program.