MPINO STUDIO 2 Phase 2 · Understand Memory

This page explains the differences between P, M, D, C, T, and R memory, address notation, memory-region settings, where memory is used in a project, and special-bit memory.

Memory understanding sequence

About screenshots: Screenshots use the English user interface.

1. PLC Memory Basics

Unlike Arduino programs, PLC programs use P, M, D, C, T, and R memory. Arduino code can allocate variables from the remaining SRAM after the PLC memory regions have been allocated.

Memory holds input states, internal conditions, calculation results, timer values, and other data while the program runs. Ladder logic and Arduino C code in MPINO Studio 2 can share and use this memory.

A basic address consists of a region letter followed by a zero-based number. For example, M10 is the eleventh address in the M region, and D0 is the first address in the D region.

Comparison of the P M D C T and R memory regions

Region Unit Storage form Value range
P BIT Digital input or output state on the board 0 or 1
M BIT Internal BIT memory 0 or 1
D WORD Signed internal WORD memory -32,768 to 32,767
C WORD Counter value (signed internal WORD memory) -32,768 to 32,767
T WORD Current timer value (signed internal WORD memory) -32,768 to 32,767
R Floating Point (32 bits) Internal Floating Point memory (real-number memory) Approximately -3.4028235E38 to +3.4028235E38

Sharing Memory Between Arduino Code and Ladder Logic

Ladder logic and Arduino code use the same storage for P, M, D, C, T, and R memory. A value written on one side can be read from the same address on the other side.

Arduino code and ladder logic sharing the same PLC memory

In Arduino code, use the ladder address name directly or write it in array form. Both forms refer to the same memory.

  • Ladder M0 ↔ Arduino code M0 or M[0]
  • Ladder D0 ↔ Arduino code D0 or D[0]
  • Ladder R0 ↔ Arduino code R0 or R[0]
void loop() {
  M0 = true;    // Sets the M0 bit contact in the ladder to ON.
  D0 = 120;     // Shares the D0 integer between ladder and Arduino code.
  R0 = 23.5f;   // Shares the R0 floating-point value between both sides.
 
  ladderLoop(); // Runs the ladder logic with the values stored above.
}

A value changed by ladder logic can be read in Arduino code after ladderLoop() finishes. Within one scan, read and write order follows the position of the ladderLoop() call inside loop().

I/O mapping caution: The P region and C addresses mapped to board functions are synchronized with physical I/O during a ladder scan. Before sharing these regions with Arduino code, check the address and I/O direction under Settings → Ladder Pin Map Settings.
P address caution: P addresses can be reviewed and changed in Board Pin Editing. Their I/O directions and physical terminals follow the definition of the board selected for the project.
R value error caution: Because of the limits of 32-bit floating-point arithmetic, 0.1 + 0.2 may be stored as approximately 0.30000001 instead of exactly 0.3. This characteristic must be considered on controllers that use IEEE 754 32-bit floating point.

Use Arduino Variables in Ladder

Global variables declared outside functions in a .ino code file can be entered by name in ladder contacts, coils, comparison contacts, and box-function arguments. The variable name must match the Arduino code exactly, including letter case.

bool motorOn = false;  // Used as motorOn in contacts and coils.
uint16_t flags = 0;    // Used in contacts and coils with a bit number, such as flags.3.
int speed = 0;         // Used in comparison contacts such as speed > 100, or as a box-function argument.

Ladder cells that use Arduino variable names

Class Supported C types Use in contacts and coils
Bit bool, boolean Enter the name as is
Byte char, signed char, unsigned char, int8_t, uint8_t, byte Add a bit number from .0 to .7
Word int, unsigned int, short, unsigned short, int16_t, uint16_t, word Add a bit number from .0 to .15
Double-word long, unsigned long, int32_t, uint32_t Add a bit number from .0 to .31
Floating-point float, double Not available (use a comparison contact such as temp > 30.5)

Variables of every class can be used in comparison contacts and box-function arguments. They cannot be used in the following cases.

  • A const variable is read-only, so it cannot be used as a coil or as a box-function argument that is written.
  • Arrays, structures, String, pointers, static variables, variables declared together on one line, variables inside an #if block, and variables in .cpp or .h files cannot be used.
  • A name shaped like a ladder address, such as M0, WM0, or D200, is always read as a ladder address.
  • Arduino variables cannot be timer or counter targets or presets, and they cannot be used in the SHL, SHR, ROL, ROR, WNOT, INV, H2D, D2H, GMOV, FMOV, SCALE, FLOOR, and SQRT commands.

In the candidate list of the cell editor, an Arduino variable appears as “Variable · code file name”. A symbol name spelled exactly like an Arduino variable is an error, and the project cannot be built. If the names differ only in letter case (for example, symbol Speed and variable speed), a warning appears in the Problems tab when you build. In that case, cells that take a single address, such as contacts and coils, and argument fields that take an address in a structured box function use the symbol even if you enter the variable name. Comparison contacts and free-form box-function expressions use the Arduino variable. If you enter a variable that cannot be used, the reason appears in the Problems tab when you build.

Ladder monitoring does not receive Arduino variable values, so variable cells are not shown as ON or OFF, and hovering over such a cell shows “Arduino variable values are not monitored”. Values cannot be written to Arduino variables with the Write Value to Arduino popup or with Ctrl + 1 / Ctrl + 0.

2. Memory Regions

The MPINO-8A4R(T)-S board uses these default memory counts:

You can change the number of addresses used under Settings → Memory Area Settings. (Shortcut: Ctrl + Shift + M)

Figure 1. Memory Area Settings for address counts, estimated SRAM use, and timer units

Region Default count Default address range
P 64 P0 to P63
M 1,024 M0 to M1023
D 200 D0 to D199
C 100 C0 to C99
T 128 T0 to T127
R 50 R0 to R49

Memory Area Settings: Blank P, M, D, C, T, and R fields use the board defaults. Entering a value changes the count for that project. The bottom of the dialog shows estimated SRAM use together with total SRAM.

In Timer units at the bottom of the dialog, you can also select the length of one timer tick (1 ms or 10 ms for T* timers; 10 ms, 100 ms, or 1000 ms for TA* timers). The selected values are saved in the project. See Phase 4-1 · Timer Unit Settings for details.

Do not confuse a count with the last address. Numbering begins at zero, so 200 D addresses run from D0 through D199.

C Region and Board Pin Mapping

On MPINO-8A4R(T)-S, analog inputs, NTC temperature inputs, and PWM are connected to C0 through C10 memory.

You can change the mapped memory under Settings → Ladder Pin Map Settings.

Analog/PWM output caution: When memory is mapped to an analog or PWM output, the value at the mapped address drives that output. You therefore cannot use analogWrite-related functions for the same output in Arduino code. To use an analogWrite-related function, clear Use for that output under Settings → Ladder Pin Map Settings.

C memory and board pin mapping on MPINO-8A4R(T)-S

C address Board function MCU pin
C0 to C5 Analog inputs A0 to A5
C6 to C7 NTC temperature inputs A6 to A7
C8 to C10 PWM outputs D21 to D23
C11 to C99 Remaining C region not directly assigned above Confirm the intended use before selecting an address
Critical check: If you choose C0 through C10 as ordinary counter addresses on this board, their data can overlap with the board functions that use the same addresses. Before assigning a counter, check Settings → Ladder Pin Map Settings and Settings → Used Memory.

Mapped addresses vary by board and can also be changed by the user. Check them under Settings → Ladder Pin Map Settings.

3. Data Types

Data width is the number of bits read or stored at one time. It determines the available value range and memory use.

BIT BYTE WORD and DWORD sizes and ranges

Width Size Signed range Typical use
BIT 1 bit 0 or 1 Contacts, coils, and ON/OFF states
BYTE 8 bits -128 to 127 Small integers
WORD 16 bits -32,768 to 32,767 General integers and the basic values of D, C, and T
DWORD 32 bits -2,147,483,648 to 2,147,483,647 Large integers beyond the WORD range

The R region also uses 32 bits, but it stores a floating-point value, not a DWORD integer. Do not treat R memory as DWORD access simply because both use 32 bits.

When selecting a width, consider the largest value after calculations. A value incremented every 1 ms for one day reaches 86,400,000 and therefore exceeds the WORD range.

4. Read Memory Addresses

Read memory addresses by starting with the simplest form and adding the required elements one at a time.

The M0, D0, D0.1, and WM1.2 memory address formats

  1. M0: BIT address 0 in the M region.
  2. D0: WORD address 0 in the D region.
  3. D0.1: the second bit in the D0 WORD. Bit numbering starts at zero.
  4. WM1.2: the third bit in WM1, the WORD view of the M region. It refers to the same bit as M18.

Memory Structure

This diagram shows the memory structure for bits, bytes, words, double words, and floating-point values.

How P and M bits and D C and T WORDs combine into BYTE WORD and DWORD views

The P and M regions group individual BIT addresses in sets of 8, 16, or 32 for BYTE, WORD, and DWORD views. The lowest address is the least significant bit, so WM0.0 refers to M0, and WM1.3 refers to M19.

Each D, C, or T address is one WORD. Two consecutive WORDs form a DWORD: DD0 combines D0 and D1, while DD1 combines D2 and D3. C and T use the same rule through forms such as DC0 and DT0.

5. Find Memory Used by the Project

Select Settings → Used Memory, or press Ctrl+Shift+L.

Figure 2. Addresses and references in Used Memory

Marker Item Action
① Area tabs Switches among the P, M, D, C, T, and R areas. P and M show 16 bits per row; D, C, T, and R show one address per row.
② Ladder and Code Show or hide the addresses used by the ladder and by Arduino code.
③ Search address Enter an address such as D5 and press Enter to switch to its area tab and highlight its row.
④ Used cells Blue cells are used by the ladder, green cells by Arduino code, and purple cells by both. Select a cell to open the usage dialog.

If a ladder cell is selected when you open this dialog, the tab and row for that cell's address appear immediately.

Usage dialog listing the ladder cells and code lines that use D5

Marker Item Action
① Usage locations For the ladder, shows the ladder name and cell position (R row number, C column number); for Arduino code, shows the file name and line number.
② Go to Moves to that ladder cell or code file and closes the Used Memory dialog.

Inspecting this map before reassigning an address or reducing a memory-region size helps prevent duplicate use and out-of-range references.

6. Special-Bit Memory

Special-bit memory beginning with @ is updated automatically by MPINO Studio 2. It can be used in ladder bit contacts.

Format Operation Example
@ON Always ON Keeps a bit contact true
@OFF Always OFF Keeps a bit contact false
@<ms> Turns ON for one scan once each specified time boundary @100 is ON for one scan every 100 ms
@F<ms> Repeats ON for the specified duration, then OFF for the same duration @F1000 repeats 1 second ON and 1 second OFF

@ON and @OFF are case-insensitive, so @on and @off are also valid.

Timing comparison of @100 and @F1000 special-bit memory

@100 still produces one ON scan when the program scan crosses a 100 ms boundary without landing exactly on it. It can start an operation or increment a value at regular intervals.

@F1000 provides a repeating one-second condition without code that manually toggles a state.

Figure 3. Special-bit memory entered in a ladder cell

Follow these input rules:

  • The time unit for @<ms> and @F<ms> is milliseconds (ms).
  • Do not use parentheses. Enter @F1000, not @F(1000).
  • Use special-bit memory only in bit contacts.
  • Do not enter it as an output-coil address.

Troubleshooting

Symptom What to check
An entered address is rejected. Check the region letter, address range, B/W/D prefix support, and .n bit-access support.
Memory Area Settings cannot be saved. Check whether estimated SRAM use exceeds total SRAM and is shown in red.
An address does not appear in Used Memory. Select the correct region tab and ladder/code filters, enter the address, and press Enter.
A C counter value is unexpected. First check for overlap with the C0 through C10 board pin mapping on MPINO-8A4R(T)-S.
@F1000 cannot be entered. Confirm that the selected cell is a bit contact and that no parentheses are present.