MPINO STUDIO2 · Changing a Timer Preset from the HMI
HMI Connection · Finding and Testing Modbus Addresses
An operator changes a delay on the touch panel, and the machine uses the new value at once, without a new upload. In MPINO STUDIO2 V2.2.0 and later, a timer can take its preset from a memory address such as D10, and the HMI writes the preset to D10 over Modbus RTU. This page sets up the rung, the HMI elements, and the scaling, and lists what to check before commissioning. The timer rules themselves are in Phase 4-1 · Set the Preset from Memory.
Earlier versions accept only a number or a time as a preset. The examples use an MPINO-8A8R-S with a channel set to Modbus RTU Slave, as in Connecting an HMI with Modbus RTU.
1. Build the rung
| Row | Condition | Output |
|---|---|---|
| 1 | NO contact M0 | Box function TON T0 D10 |
| 2 | NO contact T0 | Output coil P32 |
- While
M0is ON, timerT0counts. - When the elapsed count reaches the value in
D10, theT0contact closes and outputP32turns on. - The HMI writes the preset into
D10. The ladder does not change, and nothing is uploaded again.
Select Use for P32 under Settings → Ladder Pin Map Settings, and check under Settings → Memory Area Settings that the D area covers D10.
The same form works for all ten timers and for counters, for example CTU C12 D20. On the MPINO-8A8R-S, C0 to C11 are mapped to board functions, so the counter example starts at C12.
2. Connect the HMI elements
| HMI element | Memory | Modbus area and function | 0-based address |
|---|---|---|---|
| Preset input | D10 | Holding register, write with 06 | 2010 |
| Elapsed count display | T0 current value | Holding register, read with 03 | 4000 |
| Run switch and run lamp | M0 | Coil, write with 05 and read with 01 | 1000 |
| Done lamp | T0 done contact | Coil, read with 01 | 4000 |
Holding register 4000 and coil 4000 are different values: the register is the elapsed count, and the coil is the done contact. The elapsed count is in the same units as the preset, so an “elapsed / preset” display uses the same scaling for both. For 1-based and 4xxxx address forms, see Enter the number your HMI driver expects.
3. Scale the value
The timer reads D10 as a count of timer units, not as a time.
| Timer family | Default unit | D10 = 300 means |
|---|---|---|
T* (TON, TOFF, TPL, TMON, TMR) | 10 ms | 3 s |
TA* (TAON, TAOFF, TAPL, TAMON, TAMR) | 100 ms | 30 s |
To let the operator enter seconds with one decimal place, scale the HMI numeric input before it writes: ×100 for a T* timer at 10 ms (3.0 s is written as 300), or ×10 for a TA* timer at 100 ms (3.0 s is written as 30). Scaling options differ between HMI makers, so check the HMI manual.
The units are a project setting (Timer Unit Settings). If the unit changes later, the value in D10 keeps its count and the time changes. The Change timer units window does not convert memory presets, so update the HMI scaling as well.
4. Check before commissioning
- Limit the input range. The timer reads the preset as unsigned, so a
D10shown as −1 is 65,535 counts. With a signed 16-bit HMI object, limit the input to 0 to 32,767. - Keep the value through a power cycle.
D10is 0 after power-up until the HMI writes it, and with 0 theTONcompletes as soon asM0turns on. RegisterD10in EEPROM Retain (Ctrl+Shift+E). - Expect changes on the next scan. Raising the value while
T0runs extends the count. Lowering it below the elapsed count ends the timer on the next scan.
5. Update an existing project
- Start MPINO STUDIO2 with an internet connection. It checks for updates at start-up; select Update Now, or use Help → Check for Updates.
- Open the project and replace the numeric preset with the register, for example
TMON T0 300becomesTMON T0 D10. - Build and upload again. The board needs the new program before the memory preset works.
- Press
Ctrl+M, write a test value such as300toD10with Write Value to Arduino or from the HMI, and watchT0count.
A project saved with a timer unit other than the defaults does not open in versions older than V2.2.0. Projects left at the default units still do.