Table of Contents
MP STUDIO 2 Phase 2 · Screen Layout
MP STUDIO 2 puts the ladder canvas in the middle of the screen and arranges the tools and information panels around it. The panels sit in columns on the left and right so that they do not cover the ladder, and you can show only the panels you need.
| No. | Area | Role |
|---|---|---|
| ① | Top band | File and tool buttons, document name, PLC status indicator, and the Simulate, Connect, Monitoring and Download buttons |
| ② | Strip row | Menus, program tabs, command bar (find and zoom) and panel toggle buttons |
| ③ | Symbol rail | Buttons for placing contacts, coils and wires (F2 to F12) and the Functions button that opens the Insert Function window |
| ④ | Functions panel | Function categories, search and the bookmark list |
| ⑤ | Ladder canvas | Where you edit rungs and where monitoring values are shown |
| ⑥ | Inspector | Address, symbol name, comment, current value and uses of the selected cell |
| ⑦ | Watch card | Values of the addresses registered in the Data Table |
Depending on the situation, status indicators are shown at the bottom of the right column.
Top Band
- ① File buttons: New, Open, Save, Save As
- ② Document name: the name of the project file you are editing (
.mpx, or the.mplyou opened) - ③ PLC status indicator: connection state, model, and the scan time (SCAN) while monitoring
- ④ Tool buttons: Find & Replace, Used Data, Symbol Table, Device, Mnemonic, Communication, Options
- ⑤ Run buttons: Simulate, Connect (Ethernet connection), Monitoring, Download
Hover over a button to see its name and shortcut. Connect is shown only when the download channel is ETHERNET.
PLC Status Indicator
The PLC status indicator shows the state of the connection to the PLC in one place.
| Shown as | Meaning |
|---|---|
| Not connected | No PLC is connected. |
| Blinking dot | Waiting for the Ethernet connection to be established. |
| Ethernet connected · address | Connected to the PLC over Ethernet. |
| Monitoring · port · SCAN | Monitoring; the PLC scan time is shown. |
| Monitoring · SIM | A simulation is running (Phase 8). |
| Monitoring (fixed areas only) | The program check did not pass, so only the fixed memory areas are being read. |
| No response | The PLC stopped responding during monitoring. |
| Forced N | N points are forced. Click it to open the Force Input/Output window. |
| PLC program differs | The ladder was edited after the download. The PLC is still running the previous program. |
Strip Row
- ① Menus: Project, Edit, View, Search, Run, Settings, Help
- ② Program tabs: split the program into several tabs. Click + to add a tab.
- ③ Command bar: the address search box (
Ctrl+F), the Zoom Out, Zoom In and Fit to Width buttons, and the zoom level - ④ Panel toggle buttons: show or hide the Symbol Rail, Functions, Inspector, Watch, Command Bar and Status Indicators. The rightmost button hides all panels.
Program Tabs
Click + (Add tab) to the right of the tabs to create a new numbered tab such as Program 2. Double-click a tab name to rename it in place. Right-click a tab to open a menu with Rename Tab, Delete Tab, Duplicate Tab and Move Selected Rungs to This Tab. The first tab is named Main by default.
- Row numbers start from 0 on every tab.
- The PLC receives a single program made of the tabs joined in order.
- Switch tabs with
Ctrl+PageUpandCtrl+PageDown, and move a tab withCtrl+Shift+PageUpandCtrl+Shift+PageDown. You can also drag a tab to change the order.
Symbol Rail and Functions Panel
The symbol rail buttons do the same thing as the function keys, and each button shows its function key below the symbol. The Functions button at the bottom opens the Insert Function window (the same as Ctrl+E). Show or hide the Functions panel with Alt+2. The placement rules are described in Phase 3, and the Functions panel in Phase 4.
Ladder Canvas
The ladder canvas shows rungs row by row, with power flowing from the left power rail to the right. Click a row number on the left to select the whole row.
- ① Row numbers: start from 0 on every tab.
- ② Cursor: the cell that is currently selected.
- ③ Error cell (red): a cell with a problem that prevents downloading.
- ④ Warning cell (orange address text): a cell that can be downloaded but should be checked.
The vertical bar on the right side of the canvas shows small colored marks where error and warning cells are.
Zoom in and out with Ctrl+= and Ctrl+-, and return to 100% with Ctrl+0. Select View → Fit to Width to fit one row to the width of the canvas.
Inspector
The Inspector shows information about the cell under the cursor.
- ① Element and address: the element type of the cell (NO, NC, Coil, Fn and so on), its address, and its tab, row and column
- ② Address, Symbol name and Comment: the name and description registered in the symbol table. Click the pencil button to edit them.
- ③ Add to Watch: adds this address to the Data Table and the Watch card. An address that is already registered is shown as Watching.
- ④ Used at: a list of the cells that use the same address. Click a line to go to that cell.
During monitoring and simulation, the Current value is shown as well, and bit addresses get ON and OFF buttons next to the Force label. If the cell has a problem, the reason is shown at the bottom of the Inspector.
Watch Card
The Watch card shows the addresses and values registered in the Data Table in a compact form in the right column. The watch list is remembered separately for each project file.
When there are no addresses to watch, No addresses to watch is shown. Click the Data Table button at the bottom right of the card to open the Data Table window.
Status Indicators
The status indicators show the connection state and model, the number of cells, the number of selected cells, the check result (Check OK or Cells with errors: N), the scan time (SCAN TIME) and firmware version while monitoring, and the open file name as small items. They appear at the bottom of the right column when the Inspector is shown, and at the bottom right of the canvas when it is hidden.
The connection state and model are also shown in the PLC status indicator in the top band. How to move between error and warning cells is described in Phase 6 · Program Check.
Showing and Hiding Panels
You can show and hide panels from the View menu, with the panel toggle buttons at the right of the strip row, or with keyboard shortcuts. Which panels are shown is kept for the next launch.
| Shortcut | Panel |
|---|---|
Alt+1 | Symbol Rail |
Alt+2 | Functions |
Alt+3 | Inspector |
Alt+4 | Watch |
Alt+6 | Command Bar |
Alt+7 | Status Indicators |
Alt+0 | Hide All Panels (press again to show them) |
Quick Actions
Press Ctrl+K to open the Quick Actions window. Type part of a menu item name to find it and press Enter to run it. Each match shows the menu it belongs to and its shortcut.