User Tools

Site Tools


en-us_commands:reference:ianalogwriteinit

IanalogWriteInit()

IanalogWriteInit() sets the maximum, minimum and mode of the MPAINO analog output.

IanalogWriteInit command operation flow

void IanalogWriteInit(uint8_t ch, uint32_t maxValue = 65535UL, uint32_t minValue = 0, bool mode = false)

Commands

Command Arguments Return Value Operation
IanalogWriteInit(ch, maxValue, minValue, mode) uint8_t ch
uint32_t maxValue = 65535UL
uint32_t minValue = 0
bool mode = false
void Sets the maximum, minimum and mode of the MPAINO analog output.

Example

This example uses MPAINO-8A8R(T) with a Y output module and Analog Output Module → Y selected. It sets CH0 to a 0–1000 range and outputs its midpoint.

void setup() {
  IanalogWriteInit(0, 1000, 0, false);  // Set Y module CH0 to a 0–1000 range.
}
 
void loop() {
  IanalogWrite(0, 0, 1000, 500);  // Output the midpoint of the configured range.
  delay(500);
}

Precautions

  • Match the module DIP switches, external power supply and output range.
  • Do not configure these together with PWM functions sharing the same timer.
  • Do not output values to uninitialized channels.
  • Currently, MPAINO Y analog output supports channels up to 0~11; do not use 12~15.
  • analogWriteInit(), analogWriteFreq() and analogWriteMax() are for Y analog output channels and must not be used for high-speed pulse channels 20~31.
  • Do not use high-speed pulse GPIO numbers 130~141 with analogWrite().