IpidItermLimit()
IpidItermLimit() limits the minimum and maximum of the PID integral term.
void IpidItermLimit(uint8_t id, float iMin, float iMax)
Commands
| Command | Arguments | Return Value | Operation |
|---|---|---|---|
IpidItermLimit(id, iMin, iMax) | uint8_t id — PID loop number. Supports 0 ~ 255float iMinfloat iMax | void | Limits the minimum and maximum of the PID integral term. |
Example
This example reads the raw A0 analog value (0–1023) on MPINO-16A8R8T for the PID calculation. It shows the result only in Serial Monitor and does not drive an output. Check the A0 voltage/current setting for the connected sensor.
const uint8_t PID_ID = 0; void setup() { Serial.begin(115200); IpidSet(PID_ID, 2.0F, 0.4F, 0.1F, 100, 0.0F, 1023.0F); // Set PID gains, sample interval, and output range. IpidItermLimit(PID_ID, -100.0F, 100.0F); // Limit the integral term to -100 through 100. } void loop() { const float currentValue = analogRead(A0); // Read the raw ADC value from A0. const float result = IpidRun(PID_ID, currentValue, 512.0F); // Calculate PID output from the A0 raw value and setpoint 512. Serial.println(result); delay(100); }
Precautions
- PID output can directly affect field equipment. Begin testing with a low output range and small gains.
IpidRun()retains the previous output until thesampleMsinterval has elapsed. It may be called repeatedly inloop().- The integral term is automatically constrained by the output limits to reduce windup. Use
IpidItermLimit()if additional limits are needed. - The derivative term is calculated from the PV change to reduce abrupt jumps caused by setpoint changes.
IpidReset()resets the integral term, previous PV and previous output value.- Use the same
idfor only one control loop.