MNET Series
MNET Series is a family of communication slave products whose digital I/O, analog I/O, temperature sensor inputs, and high-speed pulse I/O can be controlled from a master device such as a PC, HMI, or PLC using Modbus or LS Industrial Systems Cnet.
The CPU module includes DIP switches for setting the baud rate and slave address.
Supports 1 RS-232 channel, 1 RS-485 channel, and 1 UART channel.
This product does not accept downloaded user programs. Select Modbus RTU Slave or LS Industrial Systems Cnet Slave when ordering.
How to read model names
- The leading number in
8A,16A,32A, etc. is the number of digital inputs. - The number before
Ris the number of relay outputs. - The number before
Tis the number of transistor outputs. 8A8Ris a model with 8 digital inputs and 8 relay outputs.8A8Tis a model with 8 digital inputs and 8 transistor outputs.
MNET Series comparison
| Model | Communication Protocol | Digital inputs | Relay outputs | Transistor outputs | RS-232 | RS-485 | UART |
|---|---|---|---|---|---|---|---|
| MNET-8A8R | Modbus RTU LS Industrial Systems Cnet | 8 | 8 | 0 | 1 | 1 | 1 |
| MNET-8A8T | Modbus RTU LS Industrial Systems Cnet | 8 | 0 | 8 | 1 | 1 | 1 |
| MNET-16A16R | Modbus RTU LS Industrial Systems Cnet | 16 | 16 | 0 | 1 | 1 | 1 |
| MNET-32A32R | Modbus RTU LS Industrial Systems Cnet | 32 | 32 | 0 | 1 | 1 | 1 |
Optional modules provide analog I/O, temperature sensor inputs, and high-speed pulse I/O.
Optional modules
The following optional modules can be added to the product configuration. The product is assembled and shipped in the selected configuration.
Users cannot add or remove I/O modules or optional modules.
| Code | Function | Points per module | Maximum configuration |
|---|---|---|---|
| X | Analog inputs | 4 points | Up to 5 units, 20 points |
| F | PT100Ω temperature sensor input | 4 points | Up to 5 units, 20 points |
| Y | Analog outputs | 3 points | Up to 4 units, 12 points |
| K | High-speed pulse outputs | 6 points | Up to 2 units, 12 points |
The combined total of analog inputs and PT100Ω temperature sensor inputs cannot exceed 20 points.
The combined total of analog outputs and high-speed pulse outputs cannot exceed 12 points.
Products with optional modules are custom-built, so exchanges or refunds may be difficult.
Communication settings
| Item | Selection range | Setting method |
|---|---|---|
| Communication protocol | Modbus RTU Slave LS Industrial Systems Cnet Slave | Select when ordering |
| Baud rate | 9,600 / 14,400 / 19,200 / 28,800 / 38,400 / 57,600 / 76,800 / 115,200bps | 3-bit DIP switch |
| Slave address | 0~15 | 4-bit DIP switch |
| Communication terminals | RS-232 RS-485 UART | Use the port wired to the master device |