Table of Contents
MPA-48A48R
MPA Series is an assembled industrial PLC combining a CPU module with digital input and output modules.
Analog input/output, temperature sensor input, and high-speed pulse output modules can be added as options.
The selected I/O and optional modules are assembled and shipped as one product. Users cannot add or remove modules.
MPA-48A48R provides 48 digital inputs and 48 relay outputs.
Program with ladder logic using MP STUDIO.
Product Specifications
| Category | Quantity | Terminal / Item | Specifications |
|---|---|---|---|
| Programming method | - | - | MP STUDIO MP STUDIO2 (Ladder logic program) |
| Power | - | Supply voltage | DC 12~24V For DC 24V, a power supply rated 0.5A or more is recommended |
| Digital inputs | 48 points (Isolated) | Module 0: P0~P7 Module 1: P8~P15 Module 2: P16~P23 Module 3: P24~P31 Module 4: P32~P39 Module 5: P40~P47 | Operating input voltage DC 0~80V HIGH detection: DC 5V or higher Optocoupler isolation |
| Relay outputs | 48 points (Isolated dry contacts) | Module 0: P64~P71 Module 1: P72~P79 Module 2: P80~P87 Module 3: P88~P95 Module 4: P96~P103 Module 5: P104~P111 | DC 0~30V or AC 0~250V Max. 5A/1 points, 8A/1COM |
| Optional modules | up to 20 points | Analog inputs PT100Ω temperature sensor input | Optional specifications |
| up to 12 points | Analog outputs High-speed pulse outputs | Optional specifications | |
| Communication Channels | 1 channel each | RS-232 RS-485 UART I²C | Built into the CPU module |
| Memory | - | Flash Data | 256KB 8KB |
Digital inputs
See the one-channel digital-input check before wiring for the first time. →
The diagram shows a wiring example for module 0. For other modules, use the corresponding contact numbers in the table. This example uses a DC 24V supply; each group can use PNP or NPN depending on its COM wiring.
The digital inputs are isolated by optocouplers. NPN or PNP switches and sensors can be used depending on the COM terminal wiring of each input module.
Relay outputs
See the one-channel relay-output check before wiring for the first time. →
The diagram shows a wiring example for module 0. For other modules, use the corresponding contact numbers in the table.
Relay outputs are dry contacts. When ON, the corresponding output contact connects to COM.
Optional modules
| Module | Maximum points | Function |
|---|---|---|
| Analog inputs | 20 points | DC 0~5V, DC 0~10V, 0~20mA or NTC temperature sensor input |
| PT100Ω temperature sensor input | 20 points | 2-wire or 3-wire PT100Ω temperature sensor input |
| Analog outputs | 12 points | DC 0~5V, DC 0~10V or 0~20mA output |
| High-speed pulse outputs | 12 points | Pulse output up to 1MHz |
Communication and program upload
The I²C diagram shows a connection example for a 5V device. Check the other device's signal voltage before connecting UART.
Status LED
Control the CPU module STATUS LED with the @SLED contact in MP STUDIO.
Development environment setup
- Connect the computer to the CPU module DOWNLOAD port with a USB cable.
- Check the download port's COM number in Device Manager.
- In MP STUDIO, open the
MPAtab and selectMPA-48A48R(T). - Set the verified COM number as the download port, then download the ladder program.
Dimensions
| Item | Dimensions |
|---|---|
| Product width | 190mm |
| Body height | 108mm |
| Overall height | Clip open: 120.42mm Clip closed: 115.16mm |
| Product depth | Body: 79mm Maximum with terminals: 83mm |
| Mounting hole spacing | 162mm |
| Mounting hole diameter | Ø4mm |
| DIN rail | 35mm |