MPA Y Module
The Y module adds three analog output channels to an MPA Series controller. Each channel's DIP switch and MP STUDIO function block determine the output range. Y and K modules can provide up to 12 output channels in total.
Select the output range
| DIP switch | Function block | V+ terminal | I+ terminal |
|---|---|---|---|
| ON | DAC | DC 0–5 V | DC 0–10 mA |
| ON | DAC2 | DC 1–5 V | DC 2–10 mA |
| OFF | DAC | DC 0–10 V | DC 0–20 mA |
| OFF | DAC2 | DC 2–10 V | DC 4–20 mA |
Use V+ for voltage or I+ for current. The negative terminal is connected internally to GND. Match the DIP switch setting to the input type of the connected equipment.
Example: set an output value
With CH0's DIP switch OFF, DAC minimum 0, maximum 100, and output value 10, the V+ terminal outputs approximately 1 V. In MP STUDIO, press [ to insert DAC, then set the channel and value range.
Check before use
- Confirm that the ordered product includes a Y module.
- Connect voltage inputs to
V+and current inputs toI+after checking the receiving device's input specification. DACandDAC2have different zero points. For 4–20 mA, use DIP OFF withDAC2.- If K modules are also installed, check the combined Y/K channel count.