MPA Analog Output Y Module

The Y module adds three analog output channels to an MPA Series controller. Each channel's DIP switch and MP STUDIO function block determine the output range. Y and K modules can provide up to 12 output channels in total.

Select the output range

DIP switch Function block V+ terminal I+ terminal
ON DAC DC 0–5 V DC 0–10 mA
ON DAC2 DC 1–5 V DC 2–10 mA
OFF DAC DC 0–10 V DC 0–20 mA
OFF DAC2 DC 2–10 V DC 4–20 mA

Use V+ for voltage or I+ for current. The negative terminal is connected internally to GND. Match the DIP switch setting to the input type of the connected equipment.

Example: set an output value

With CH0's DIP switch OFF, DAC minimum 0, maximum 100, and output value 10, the V+ terminal outputs approximately 1 V. In MP STUDIO, press [ to insert DAC, then set the channel and value range.

Check before use

  • Confirm that the ordered product includes a Y module.
  • Connect voltage inputs to V+ and current inputs to I+ after checking the receiving device's input specification.
  • DAC and DAC2 have different zero points. For 4–20 mA, use DIP OFF with DAC2.
  • If K modules are also installed, check the combined Y/K channel count.

Back to MPA Series