CTD Box Function

Count Down Counter

Category: Counter Box Functions

Behavior

Preloads the current value with the set value, then decrements it once on each rising edge of the left condition. The done state turns ON at zero, where counting stops.

Syntax and Arguments

Syntax: CTD C12 3

  • Target — counter memory C<n> (16-bit) or DC<n> (32-bit)
  • preset — starting count loaded on reset. An integer or a memory address such as D10 (time units are not accepted)

Behavior Example

Run condition Before Command entered Expected result
Left condition ON C12=3 CTD C12 3 3 rising edges → C12=0, C12 done contact=ON

CTD input, current value, and done state

Cautions

  • A counter changes once per rising edge of the left condition. On MPINO-8A4R(T)-S, C0 through C10 are mapped to board functions, so use C11 or later for a counter.
  • When the preset is a memory address, CTD reads the value only at boot and when it is initialized by a RESET coil. After changing the value while running, for example from an HMI, you must turn the RESET coil on once to apply it. When the memory value is 0, the counter does not complete. For details, see Set the Preset from Memory.