User Tools

Site Tools


en-us_products:mpino_studio2:box_functions:counter:ctud

CTUD Box Function

Count Up/Down Counter

Category: Counter Box Functions

Behavior

While the left condition is ON, a rising edge on the up input adds one and a rising edge on the down input subtracts one. If both rise in the same scan, the value does not change.

Syntax and Arguments

Syntax: CTUD C11 M0 M1 3

  • Target — counter memory C<n> (16-bit) or DC<n> (32-bit)
  • up — the bit contact to increment (e.g. P0/M1)
  • down — the bit contact to decrement (e.g. P1/M2)
  • preset — count at which the done bit turns ON. An integer or a memory address such as D10 (time units are not accepted)

Behavior Example

Run condition Before Command entered Expected result
Left condition ON C11=0 CTUD C11 M0 M1 3 M0 ×2, M1 ×1 → C11=1

CTUD input, current value, and done state

Cautions

  • A counter changes once per rising edge of the left condition. On MPINO-8A4R(T)-S, C0 through C10 are mapped to board functions, so use C11 or later for a counter.
  • If you enter a memory address such as D10 as the preset, you can change the target count while running, for example from an HMI. When the memory value is 0, the counter does not complete. For details, see Set the Preset from Memory.

Box Functions in the Same Category

en-us_products/mpino_studio2/box_functions/counter/ctud.txt · Last modified: by 127.0.0.1