MPINO STUDIO2 · Connecting an HMI with Modbus RTU

← STUDIO2 installation and start · Next: Building the HMI Screen → · Optional: LS Electric Cnet →

When you set the protocol to Modbus RTU Slave in MPINO STUDIO2, the app generates the product's request-handling code. The HMI sends requests as the Modbus RTU Master. The internal D words the HMI reads and writes map to Holding Registers, and M bits map to Coils. The addresses in STUDIO2's generated code are different from those in the Arduino IDE SDK examples.

The table shows 0-based addresses inside the Modbus request that STUDIO2's generated code accepts. If your HMI takes 1-based Coil numbers, M0 may appear as 1001. For the numbers to enter in 1-based or 4xxxx notation, check the HMI driver manual and follow the HMI address format.

HMI element STUDIO2 memory Modbus area 0-based address in the request
Number that changes every second D0 Holding Register 2000
Number input D1 Holding Register 2001
Number that returns the input value D2 Holding Register 2002
Switch and check lamp M0 Coil 1000
Lamp for the ladder result M1 Coil 1001

This simple example uses only internal memory on MPINO-8A4R-S · RS-232 Serial1 · station 1 · 9600 bps · 8N1. It does not use real I/O terminals. For channels, wiring, installation, and product selection, see Wiring the HMI and STUDIO2 installation and start.

1. New project and internal memory

  1. Select MPINO-8A4R(T)-S under File → New and save the project as HMI_First_Test.mp2.
  2. Under Settings → Memory Area Settings, set P to 64 and M, D, C, T, and R to 16 each. These numbers are counts, not addresses.
  3. Under Settings → Ladder Pin Map Settings, clear Use for all physical input and output pins. This program uses only internal M and D.

MPINO STUDIO2 board selection window

The communication terminals differ by product. Check your product's port in the channel table.

2. One ladder rung and the main code

In the Explorer, open Ladder → ladderLoop. Place an NO contact (F2) M0 at row 1, column 1, and an output coil (F9) M1 at row 1, column 2. M1 is an internal bit, not a real relay output.

Exercise circuit where contact M0 drives internal coil M1

Open the main code tab under Code and enter the code below. This code goes in main of the STUDIO2 project. It is not a stand-alone sketch for Arduino IDE.

#include "mpino_runtime.h"
#include "ladder_generated.h"
 
unsigned long lastTick = 0;
 
void setup() {
  M[0] = false;
  M[1] = false;
  D[0] = 0;
  D[1] = 0;
  D[2] = 0;
  lastTick = millis();
}
 
void loop() {
  ladderLoop();
  unsigned long now = millis();
  if (now - lastTick >= 1000UL) {
    lastTick = now;
    D[0] = (D[0] + 1) % 100;
  }
  D[2] = D[1];
}

D0 repeats 0~99 once per second. When the HMI writes a number to D1, D2 follows it. When M0 turns on, the ladder turns on M1. STUDIO2 generates the communication initialization and request handling from the communication settings, so do not add ImodbusRTUInit() or ImodbusRTU() to this code.

3. Run → Communication

Enter the values in the table below. The figure shows an initial screen to locate each item. Its protocol None and baud rate 115200 are not the values for this exercise. Change them to Modbus RTU Slave and 9600, then save.

Figure no. Item Value
① Channel Serial1 — the RS-232 port on this product
② Protocol Modbus RTU Slave
③ Slave ID 1
④ Baud Rate 9600
⑤·⑥·⑦ Data Bits · Stop Bits · Parity 8 · 1 · None

Initial screen showing where each item is. The protocol None and 115200 in the figure are only an example; this exercise changes them to Modbus RTU Slave and 9600.

Enter these values under Run → Communication and press Ctrl+S to save. On the HMI side, set the RS-232 port you connected to Modbus RTU Master with the same station number and communication settings.

4. Build, upload, and HMI addresses

  1. Run Run → Build (Ctrl+R) and check for the success message in Build Output.
  2. In the status bar, select the PC COM port of the MP Download Cable for your product, then run Run → Upload (Ctrl+U). Confirm that the upload log in the bottom panel ends normally. The upload port and Serial1 for the HMI are separate connections. For screens and steps, see Select a Port and Upload.
  3. Connect the three HMI numbers and the bit switch and lamp according to the address table above. Set numbers to signed 16-bit integer, 1 word, 0 decimal places, scale 1, and set the input range to 0~9999.

Actual HMI communication in this example must be checked separately for your HMI model and cable. Do not assign the same Serial1 to ladder monitoring or user serial code as well.

First assign this page's Modbus addresses in Building the HMI Screen, then continue with Checking Operation and Troubleshooting. To try Cnet as well, switch the same program to LS Electric Cnet →.