en-us_products:mpino_studio2:box_functions:timer:toff
Table of Contents
TOFF Box Function
Off Delay Timer
Category: Timer Box Functions
Behavior
Turns the done state ON immediately with the input. After the input turns OFF, the done state turns OFF when the set time has elapsed.
Syntax and Arguments
Syntax: TOFF T0 100
- Target — timer memory T<n> (16-bit) or DT<n> (32-bit)
- Time (preset) — 10ms ticks. A number (ticks) or a time unit like 1m10s
Behavior Example
| Run condition | Before | Command entered | Expected result |
|---|---|---|---|
| Left condition ON → OFF | T0 done contact=ON | TOFF T0 100 | 1 s later → T0 done contact=OFF |
Cautions
- A numeric time is a tick count. The TON family uses 10 ms per tick, and the TAON family uses 100 ms per tick.
Box Functions in the Same Category
- TON View details — On Delay Timer
- TPL View details — Pulse Timer
- TMON View details — Monostable / One-shot Timer
- TMR View details — Retentive Timer
- TAON View details — On Delay Timer · 100ms
- TAOFF View details — Off Delay Timer · 100ms
- TAPL View details — Pulse Timer · 100ms
- TAMON View details — Monostable Timer · 100ms
- TAMR View details — Retentive Timer · 100ms
en-us_products/mpino_studio2/box_functions/timer/toff.txt · Last modified: by 127.0.0.1