TAMR Box Function

Retentive Timer · 100ms

Category: Timer Box Functions

Behavior

Provides the same retentive behavior as TMR with a default 100 ms tick. Use a ladder RESET coil to initialize it.

Syntax and Arguments

Syntax: TAMR T0 100

  • Target — timer memory T<n> (16-bit) or DT<n> (32-bit)
  • Time (preset) — 100ms ticks by default (10ms, 100ms, or 1000ms in the settings). A number (ticks), a time unit like 1m10s, or a memory address such as D10

Behavior Example

Run condition Before Command entered Expected result
Left condition ON T0=40 TAMR T0 100 6 seconds (60 ticks, default unit) → T0=100, T0 done contact=ON

TAMR input, current value, and done state

Cautions

  • A numeric time is a tick count. By default, the TON family uses 10 ms per tick and the TAON family uses 100 ms per tick; you can change this for each project in Timer Unit Settings. Changing the unit also changes the actual time of a numeric value.
  • If you enter a memory address such as D10 in the time field, you can change the time while running, for example from an HMI. The memory value is a tick count, not a time: with the default unit, TAMR T0 D10 uses 5 seconds when D10 is 50. For details, see Set the Preset from Memory.
  • Use a ladder RESET coil, rather than box-function RST, to initialize the current and done states.