en-us_products:mpino_studio2:box_functions:timer:ton

TON Box Function

On Delay Timer

Category: Timer Box Functions

Behavior

Accumulates time while the input is ON and turns the done state ON at the set value. When the input turns OFF, the current and done states reset to zero.

Syntax and Arguments

Syntax: TON T0 100

  • Arg 1 = target: timer memory T<n> (16-bit) / DT<n> (32-bit), stores the elapsed value
  • Arg 2 = time: 10ms ticks by default (1ms or 10ms in the settings). Accepts 100 (=100 ticks, 1s with the default unit), a time literal like 1m10s, or a memory address such as D10

Behavior Example

Run condition Before Command entered Expected result
Left condition ON T0=0 TON T0 100 1 s later (default unit) → T0=100, T0 done contact=ON

TON input, current value, and done state

Cautions

  • A numeric time is a tick count. By default, the TON family uses 10 ms per tick and the TAON family uses 100 ms per tick; you can change this for each project in Timer Unit Settings. Changing the unit also changes the actual time of a numeric value.
  • If you enter a memory address such as D10 in the time field, you can change the time while running, for example from an HMI. The memory value is a tick count, not a time: with the default unit, TON T0 D10 uses 5 seconds when D10 is 500. For details, see Set the Preset from Memory.

Box Functions in the Same Category

en-us_products/mpino_studio2/box_functions/timer/ton.txt · Last modified: by 127.0.0.1