en-us_products:mpino_studio2:box_functions:timer:taoff
Table of Contents
TAOFF Box Function
Off Delay Timer · 100ms
Category: Timer Box Functions
Behavior
Provides the same off-delay behavior as TOFF with a default 100 ms tick.
Syntax and Arguments
Syntax: TAOFF T0 100
- Target — timer memory T<n> (16-bit) or DT<n> (32-bit)
- Time (preset) — 100ms ticks by default (10ms, 100ms, or 1000ms in the settings). A number (ticks), a time unit like 1m10s, or a memory address such as
D10
Behavior Example
| Run condition | Before | Command entered | Expected result |
|---|---|---|---|
| Left condition ON → OFF | T0 done contact=ON | TAOFF T0 100 | 10 s later (default unit) → T0 done contact=OFF |
Cautions
- A numeric time is a tick count. By default, the TON family uses 10 ms per tick and the TAON family uses 100 ms per tick; you can change this for each project in Timer Unit Settings. Changing the unit also changes the actual time of a numeric value.
- If you enter a memory address such as
D10in the time field, you can change the time while running, for example from an HMI. The memory value is a tick count, not a time: with the default unit,TAOFF T0 D10uses 5 seconds when D10 is 50. For details, see Set the Preset from Memory.
Box Functions in the Same Category
- TON View details — On Delay Timer
- TOFF View details — Off Delay Timer
- TPL View details — Pulse Timer
- TMON View details — Monostable / One-shot Timer
- TMR View details — Retentive Timer
- TAON View details — On Delay Timer · 100ms
- TAPL View details — Pulse Timer · 100ms
- TAMON View details — Monostable Timer · 100ms
- TAMR View details — Retentive Timer · 100ms
en-us_products/mpino_studio2/box_functions/timer/taoff.txt · Last modified: by 127.0.0.1