TPL Box Function

Pulse Timer

Category: Timer Box Functions

Behavior

Turns the done state ON when the input changes to ON. It turns OFF when the input turns OFF or the set time expires, whichever happens first.

Syntax and Arguments

Syntax: TPL T0 100

  • Target — timer memory T<n> (16-bit) or DT<n> (32-bit)
  • Time (preset) — 10ms ticks by default (1ms or 10ms in the settings). A number (ticks), a time unit like 1m10s, or a memory address such as D10

Behavior Example

Run condition Before Command entered Expected result
Left condition turns ON once T0=0 TPL T0 100 0 s → T0 done contact=ON; 1 s later (default unit) → OFF

TPL input, current value, and done state

Cautions

  • A numeric time is a tick count. By default, the TON family uses 10 ms per tick and the TAON family uses 100 ms per tick; you can change this for each project in Timer Unit Settings. Changing the unit also changes the actual time of a numeric value.
  • If you enter a memory address such as D10 in the time field, you can change the time while running, for example from an HMI. The memory value is a tick count, not a time: with the default unit, TPL T0 D10 uses 5 seconds when D10 is 500. For details, see Set the Preset from Memory.